Location 187-202: Special Communicator Reporting Characteristics For Zones
1-16
Locations 187-202 are used to assign communicator characteristics to individual zones 1 through 16. Location 187 is for zone-. 1 and
location 202 is for zone 16. Each zone can have one or a combination of these characteristics. Factory default for all zones is "11" (1 +
2 + 8 ="11 "). This means that each zone has
Restore Reporting (Value=1), Isolate Reporting (Value=2),
and
Report Canceling
(Value=8)
enabled. It should be noted that these locations are used to enable individual zone report capability by zone. A reporting
code must be programmed in the appropriate location to enable overall reporting capability of
Restore
reports (location 364),
Isolate
reports (Location 368),
Trouble/24 Hour Tamper
reports (location 372), and
Cancel
reports (location 354).
VALUE
REPORTING CHARACTERISTICS
1
Restore Reporting
2
Isolate Reporting
4
Trouble/24 Hour Tamer Reporting
8
Report Canceling
Location 203: Programming The Communicator To Abort
Location 203 is used to enable the communicator
Abort.
A "1" in this location will cause the DL-300E to abort the report of a trip on
any non-24 hour zone, if an arm/disarm code is entered during the delay of line seizure (see location 221). If this location contains a
"0", the DL-300E will not abort any reports. NOTE! The DL-300E will not abort unless a delay time is programmed in location 221.
Location 204: Immediate Restore By Zone
If a "1" is programmed in location 204 restore signals will follow the restore condition and report restores immediately after the
condition has restored. A non-extended format will not send a
Restore
message until all zones and
Trouble
conditions have
restored. If this location contains a "0", the
Restore
signal(s) will be reported only after siren timeout. Factory default is "1"
enabled.
Location 205: Auto Isolate
Location 205 is used to enable the
Auto Isolate
feature. If a "1" is programmed in this location, the DL-300E will allow the user to
enter a valid code to arm when one or more zones are not secure. If these zones clear before the end of either exit delay, they will
arm with the remainder of the zones when the exit delay time expires. All zones which are unsecured at the end of the exit delay
will be automatically isolated. If isolate reporting has been enabled in location 368, all automatically isolated zones will be reported
to the monitoring station.
Location 206: Programming For Silent Code pad Panic
Location 206 is used to silence the audible output for the
Code pad Panic/Hold-Up
alarm. Programming a "1" in this location will
enable the
Silent
mode of
Code pad Panic operation.
Factory default is "0" and operation of the
Code pad Panic
(double
keypress [*] & [#]) will cause the yelp siren output to activate.
Location 207: Reserved