Figure 3.9 Adjustable Warnings
4-50 Warning Current Low
Range:
Function:
0.00 A
*
[Application
dependant]
Enter the I
LOW
value. When the motor
current falls below this limit, the display
reads
Current Low
. The signal outputs
can be programmed to produce a
status signal on terminal 27 or 29 (FC
302 only) and on relay output 01 or 02
(FC 302 only). Refer to
Figure 3.9
.
4-51 Warning Current High
Range:
Function:
Application
dependent
*
[Application
dependant]
Enter the I
HIGH
value. When the
motor current exceeds this limit,
the display reads
Current High
.
The signal outputs can be
programmed to produce a status
signal on terminal 27 or 29 (FC
302 only) and on relay output 01
or 02 (FC 302 only). Refer to
Figure 3.9
.
4-52 Warning Speed Low
Range:
Function:
0 RPM
*
[Application
dependant]
Enter the n
LOW
value. When the motor
speed exceeds this limit, the display
reads
Speed Low
. The signal outputs
can be programmed to produce a
status signal on terminal 27 or 29 (FC
302 only) and on relay output 01 or 02
(FC 302 only).
4-53 Warning Speed High
Range:
Function:
Application
dependent
*
[Application
dependant]
Enter the n
HIGH
value. When the
motor speed exceeds this limit, the
display reads
Speed High
. The
signal outputs can be
programmed to produce a status
signal on terminal 27 or 29 (FC
302 only) and on relay output 01
or 02 (FC 302 only). Program the
upper signal limit of the motor
speed, n
HIGH
, within the normal
working range of the Adjustable
frequency drive. Refer to
Figure 3.9
.
4-54 Warning Reference Low
Range:
Function:
-999999.999
*
[Application
dependant]
Enter the lower reference limit.
When the actual reference falls
below this limit, the display
indicates Ref Low. The signal
outputs can be programmed to
produce a status signal on
terminal 27 or 29 (FC 302 only)
and on relay output 01 or 02 (FC
302 only).
4-55 Warning Reference High
Range:
Function:
999999.999
*
[Application
dependant]
Enter the upper reference limit.
When the actual reference exceeds
this limit, the display reads Ref
High. The signal outputs can be
programmed to produce a status
signal on terminal 27 or 29 (FC 302
only) and on relay output 01 or 02
(FC 302 only).
4-56 Warning Feedback Low
Range:
Function:
-999999.999
ReferenceFeed-
backUnit
*
[Application
dependant]
Enter the lower feedback
limit. When the feedback falls
below this limit, the display
reads Feedb Low. The signal
outputs can be programmed
to produce a status signal on
terminal 27 or 29 (FC 302
only) and on relay output 01
or 02 (FC 302 only).