13-10 Comparator Operand
Array [6]
Option:
Function:
Feedback Low
and
4-57 Warning
Feedback High
.
[76]
Below feedb.
low
Below feedb. Low
[76] The feedback is
below the limit set in
4-56 Warning
Feedback Low
.
[77]
Above feedb.
high
Above feedb. High
[77] The feedback is
above the limit set in
4-57 Warning
Feedback High
.
[80]
Thermal warning
Thermal warning
[80] The thermal
warning turns on when the temperature
exceeds the limit in the motor, the
Adjustable frequency drive, the brake
resistor or thermistor.
[82]
Mains out of
range
Line power out of range
[82] The AC line
voltage is outside the specified voltage
range.
[85]
Warning
Warning
[85] A warning is active.
[86]
Alarm (trip)
Alarm (trip)
[86] A (trip) alarm is active.
[87]
Alarm (trip lock)
Alarm (trip lock)
[87] A (Trip lock) alarm
is active.
[90]
Bus OK
Bus OK
[90] Active communication (no
timeout) via the serial communication
port.
[91]
Torque limit &
stop
Torque limit & stop
[91] If the Adjustable
frequency drive has received a stop
signal and is at the torque limit, the
signal is logic “0”.
[92]
Brake fault
(IGBT)
Brake fault (IGBT)
[92] The brake IGBT is
short circuited.
[93]
Mech. brake
control
Mech. brake control
[93] The mechanical
brake is active.
[94]
Safe stop active
[100] Comparator 0
Comparator 0
[100] The result of
comparator 0.
[101] Comparator 1
Comparator 1
[101] The result of
comparator 1.
[102] Comparator 2
Comparator 2
[102] The result of
comparator 2.
[103] Comparator 3
Comparator 3
[103] The result of
comparator 3.
[104] Comparator 4
Comparator 4
[104] The result of
comparator 4.
[105] Comparator 5
Comparator 5
[105] The result of
comparator 5.
13-10 Comparator Operand
Array [6]
Option:
Function:
[110] Logic rule 0
Logic rule 0
[110] The result of logic rule
0.
[111] Logic rule 1
Logic rule 1
[111] The result of logic rule
1.
[112] Logic rule 2
Logic rule 2
[112] The result of logic rule
2.
[113] Logic rule 3
Logic rule 3
[113] The result of logic rule
3.
[114] Logic rule 4
Logic rule 4
[114] The result of logic rule
4.
[115] Logic rule 5
Logic rule 5
[115] The result of logic rule
5.
[120] SL Time-out 0
SL Timeout 0
[120] The result of SLC
timer 0.
[121] SL Time-out 1
SL Timeout 1
[121] The result of SLC
timer 1.
[122] SL Time-out 2
SL Timeout 2
[122] The result of SLC
timer 2.
[123] SL Time-out 3
SL Timeout 3
[123] The result of SLC
timer 3.
[124] SL Time-out 4
SL Timeout 4
[124] The result of SLC
timer 4.
[125] SL Time-out 5
SL Timeout 5
[125] The result of SLC
timer 5.
[126] SL Time-out 6
SL Timeout 6
[126] The result of SLC
timer 6.
[127] SL Time-out 7
SL Timeout 7
[127] The result of SLC
timer 7.
[130] Digital input
DI18
Digital input DI18
[130] Digital input 18.
High = True.
[131] Digital input
DI19
Digital input DI19
[131] Digital input 19.
High = True.
[132] Digital input
DI27
Digital input DI27
[132] Digital input 27.
High = True.
[133] Digital input
DI29
Digital input DI29
[133] Digital input 29.
High = True.
[134] Digital input
DI32
Digital input DI32
[134] Digital input 32.
High = True.
[135] Digital input
DI33
Digital input DI33
[135] Digital input 33.
High = True.
[150] SL digital output
A
SL digital output A
[150] Use the result
of the SLC output A.
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
3-115
3
3