8-55 Set-up Select
Option:
Function:
[1]
Bus
Activates the set-up selection via the serial
communication port or serial communication
option.
[2]
Logic
AND
Activates the set-up selection via the serial
communication bus/serial communication port,
AND additionally via one of the digital inputs.
[3]
*
Logic OR
Activate the set-up selection via the serial
communication bus/serial communication port
OR via one of the digital inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the Adjustable frequency drive
Preset Reference selection via the terminals
(digital input) and/or via the serial communi-
cation bus.
[0]
Digital
input
Activates Preset Reference selection via a digital
input.
[1]
Bus
Activates Preset Reference selection via the
serial communication port or serial communi-
cation option.
[2]
Logic AND Activates Preset Reference selection via the
serial communication bus/serial communication
port, AND additionally via one of the digital
inputs.
[3]
*
Logic OR
Activates the Preset Reference selection via the
serial communication bus/serial communication
port OR via one of the digital inputs.
8-57 Profidrive OFF2 Select
Select control of the drive OFF2 selection via the terminals
(digital input) and/or via the serial communication bus. This
parameter is active only when par. 8-01 Control Site is set to [0]
Digital and ctrl. word and par. 8-10 is set to [1] Profidrive profile.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
8-58 Profidrive OFF3 Select
Select control of the drive OFF3 selection via the terminals
(digital input) and/or via the serial communication bus. This
parameter is active only when par. 8-01 Control Site is set to [0]
Digital and control word and par. 8-10 is set to [1] Profidrive
profile.
Option:
Function:
[0]
Digital input
[1]
Bus
8-58 Profidrive OFF3 Select
Select control of the drive OFF3 selection via the terminals
(digital input) and/or via the serial communication bus. This
parameter is active only when par. 8-01 Control Site is set to [0]
Digital and control word and par. 8-10 is set to [1] Profidrive
profile.
Option:
Function:
[2]
Logic AND
[3]
*
Logic OR
3.10.6 8-8* AFD Port Diagnos.
These parameters are used for monitoring the bus
communication via the Adjustable Frequency Drive Port.
8-80 Bus Message Count
Range:
Function:
0
*
[0 - 0 ] This parameter shows the number of valid
messages detected on the bus.
8-81 Bus Error Count
Range:
Function:
0
*
[0 - 0 ] This parameter shows the number of messages
with faults (e.g., CRC fault), detected on the bus.
8-82 Slave Messages Rcvd
Range:
Function:
0
*
[0 - 0 ] This parameter shows the number of valid
messages addressed to the slave, sent by the
Adjustable frequency drive.
8-83 Slave Error Count
Range:
Function:
0
*
[0 - 0 ] This parameter shows the number of error
messages, which could not be executed by the
Adjustable frequency drive.
3.10.7 8-9* Bus Jog
8-90 Bus Jog 1 Speed
Range:
Function:
100 RPM
*
[ 0 - par. 4-13
RPM]
Enter the jog speed. This is a fixed
jog speed activated via the serial
port or serial communication bus
option.
Parameter Descriptions
FC 300 Programming Guide
3-92
MG33MD22 - VLT
®
is a registered Danfoss trademark
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx