[47]
Bus Ctrl Off at
timeout
Controls output via bus. The state of the
output is set in
5-90 Digital & Relay Bus
Control
. In the event of a bus timeout,
the output state is set low (Off).
[51]
MCO controlled Active when a MCO 302 or MCO 305 is
connected. The output is controlled from
option.
[55]
Pulse output
[60]
Comparator 0
See parameter group 13-1*. If Comparator
0 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[61]
Comparator 1
See parameter group 13-1*. If Comparator
1 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[62]
Comparator 2
See parameter group 13-1*. If Comparator
2 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[63]
Comparator 3
See parameter group 13-1*. If Comparator
3 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[64]
Comparator 4
See parameter group 13-1*. If Comparator
4 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[65]
Comparator 5
See parameter group 13-1*. If Comparator
5 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[70]
Logic Rule 0
See parameter group 13-4*. If Logic Rule
0 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[71]
Logic Rule 1
See parameter group 13-4*. If Logic Rule
1 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[72]
Logic Rule 2
See parameter group 13-4*. If Logic Rule
2 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[73]
Logic Rule 3
See parameter group 13-4*. If Logic Rule
3 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[74]
Logic Rule 4
See parameter group 13-4*. If Logic Rule
4 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[75]
Logic Rule 5
See parameter group 13-4*. If Logic Rule
5 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[80]
SL Digital
Output A
See
13-52 SL Controller Action
. The output
will go high whenever the Smart Logic
Action [38]
Set dig. out. A
high is
executed. The output will go low
whenever the Smart Logic Action [32] Set
dig. out. A low is executed.
[81]
SL Digital
Output B
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action [39]
Set dig. out. A
high is
executed. The input will go low whenever
the Smart Logic Action [33]
Set dig. out. A
low
is executed.
[82]
SL Digital
Output C
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action [40]
Set dig. out. A
high is
executed. The input will go low whenever
the Smart Logic Action [34]
Set dig. out. A
low
is executed.
[83]
SL Digital
Output D
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action [41]
Set dig. out. A
high is
executed. The input will go low whenever
the Smart Logic Action [35]
Set dig. out. A
low
is executed.
[84]
SL Digital
Output E
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action [42]
Set dig. out. A
high is
executed. The input will go low whenever
the Smart Logic Action [36]
Set dig. out. A
low
is executed.
[85]
SL Digital
Output F
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action [43]
Set dig. out. A
high is
executed. The input will go low whenever
the Smart Logic Action [37]
Set dig. out. A
low
is executed.
[120] Local reference
active
Output is high when
3-13 Reference Site
=
[2] Local or when
3-13 Reference Site
= [0]
Linked to hand auto
at the same time as
the LCP is in [Hand on] mode.
Reference site
set in
3-13 Reference
Site
Local
referenc
e
active
[120]
Remote
reference
active
[121]
Reference site:
Local
3-13 Reference Site
[2]
1
0
Reference site:
Remote
3-13 Reference Site
[1]
0
1
Reference site:
Linked to Hand/
Auto
Hand
1
0
Hand -> off
1
0
Auto -> off
0
0
Auto
0
1
Parameter Descriptions
FC 300 Programming Guide
3-56
MG33MD22 - VLT
®
is a registered Danfoss trademark
3