2.1.8 Initial Commissioning
The easiest way of carrying out the initial commissioning is by using the quick menu button and follow the quick set-up
procedure using LCP 102 (read table from left to right). The example applies to open-loop applications.
Press
Quick
Menu
Q2 Quick Menu
OK
0-01
Language
OK
Set language
1-20
Motor Power [kW]
OK
Set motor nameplate power
1-22
Motor Voltage
OK
Set nameplate voltage
1-23
Motor Frequency
OK
Set nameplate frequency
1-24
Motor Current
OK
Set nameplate current
1-25
Motor Nominal Speed
OK
Set Nameplate speed in RPM
5-12 Terminal 27 Digital Input
OK
If terminal default is
Coast
inverse,
it is possible to change
this setting to
No function
. No
connection to terminal 27 is
then needed for running AMA
1-29
Automatic Motor Adaptation
(AMA)
OK
Set desired AMA function.
Enabling complete AMA is
recommended
3-02
Minimum Reference
OK
Set the minimum speed of the
motor shaft
3-03
Maximum Reference
OK
Set the maximum speed of the
motor shaft
3-41
Ramp 1 Ramp up Time
OK
Set the ramping-up time with
reference to synchronous
motor speed, ns.
3-42
Ramp 1 Ramp Down Time
OK
Set the ramping-down time
with reference to synchronous
motor speed, ns.
3-13
Reference Site
OK
Set the site from where the
reference must work
How to Program
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
2-7
2
2