130BA070.10
Time
P 3-80
RPM
P 4-13 RPM
high limit
P 1-25
Motor speed
Jog speed
P 3-19
P 3-80
Ramp up
(acc)
Ramp down
(dec)
t jog
t jog
P 4-11 RPM
low limit
Par. 3 − 80 =
tjog s x ns RPM
Δ
log speed (par. 3 − 19) RPM
3-81 Quick Stop Ramp Time
Range:
Function:
Application
dependent
*
[0.01 -
3600.00
s]
Enter the quick stop ramp-down time,
i.e., the deceleration time from the
synchronous motor speed to 0 RPM.
Ensure that no resultant overvoltage
will arise in the inverter due to
regenerative operation of the motor
required to achieve the given ramp-
down time. Ensure also that the
generated current required to achieve
the given ramp-down time does not
exceed the current limit (set in
4-18 Current Limit
). Quick stop is
activated by means of a signal on a
selected digital input, or via the serial
communication port.
Application
dependent
*
[0.01 -
3600.00
s]
Bus only
Enter the quick stop ramp-down time,
i.e., the deceleration time from the
synchronous motor speed to 0 RPM.
Ensure that no resultant overvoltage
will arise in the inverter due to
regenerative operation of the motor
required to achieve the given ramp-
down time. Ensure also that the
generated current required to achieve
the given ramp-down time does not
exceed the current limit (set in
4-18 Current Limit
). Quick stop is
activated by means of a signal on a
selected digital input, or via the serial
communication port.
130BA069.10
Time
RPM
P 4-13 RPM
high limit
Reference
P 1-25
Motor speed
low limit
P 4-11 RPM
P 3-81
Qramp
Qstop
Par. 3 − 81 =
tQstop s x ns RPM
Δ
jog ref (par. 3 − 19) RPM
3-82 Quick Stop Ramp Type
Option:
Function:
Select the ramp type, depending on
requirements for acceleration and
deceleration. A linear ramp will give
constant acceleration during ramping. An
S-ramp will give non-linear acceleration,
compensating for jerk in the application.
[0]
*
Linear
[1]
S-ramp Const
Jerk
[2]
S-ramp Const
Time
3-83 Quick Stop S-ramp Ratio at Decel. Start
Range:
Function:
50 %
*
[Application dependant]
3-84 Quick Stop S-ramp Ratio at Decel. End
Range:
Function:
50 %
*
[Application
dependant]
Enter the proportion of the total
ramp-down time (
3-42 Ramp 1 Ramp
Down Time
) where the deceleration
torque decreases. The larger the
percentage value, the greater the jerk
compensation achieved, and thus the
lower the torque jerks in the
application.
3.5.8 3-9* Digital Pot. meter
The digital potentiometer function allows the user to
increase or decrease the actual reference by adjusting the
set-up of the digital inputs using the functions
Increase
,
Parameter Descriptions
FC 300 Programming Guide
3-42
MG33MD22 - VLT
®
is a registered Danfoss trademark
3
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx