[4]
Enable / no
warning
Ready for operation. No start or stop
command is been given (start/disable).
No warnings are active.
[5]
VLT running
Motor is running and shaft torque is
present.
[6]
Running / no
warning
Output speed is higher than the speed
set in
1-81 Min Speed for Function at Stop
[RPM]
. The motor is running and there are
no warnings.
[7]
Run in
range/no
warning
Motor is running within the programmed
current and speed ranges set in
4-50 Warning Current Low
to
4-53 Warning
Speed High
. There are no warnings.
[8]
Run on
reference / no
warning
Motor runs at reference speed. No
warnings.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
warning
An alarm or a warning activates the
output.
[11]
At torque limit
The torque limit set in
4-16 Torque Limit
Motor Mode
or
4-17 Torque Limit Generator
Mode
has been exceeded.
[12]
Out of current
range
The motor current is outside the range
set in
4-18 Current Limit
.
[13]
Below current,
low
Motor current is lower than set in
4-50 Warning Current Low
.
[14]
Above current,
high
Motor current is higher than set in
4-51 Warning Current High
.
[15]
Out of speed
range
Output frequency is outside the
frequency ranges set in
4-52 Warning
Speed Low
and
4-53 Warning Speed High
.
[16]
Below speed,
low
Output speed is lower than the setting in
4-52 Warning Speed Low
.
[17]
Above speed,
high
Output speed is higher than the setting
in
4-53 Warning Speed High
.
[18]
Out of
feedback range
Feedback is outside the range set in
4-56 Warning Feedback Low
and
4-57 Warning Feedback High
.
[19]
Below
feedback low
Feedback is below the limit set in
4-56 Warning Feedback Low
.
[20]
Above
feedback high
Feedback is above the limit set in
4-57 Warning Feedback High
.
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the Adjustable frequency drive,
the brake resistor, or the thermistor.
[22]
Ready, no
thermal
warning
Adjustable frequency drive is ready for
operation and there is no over-
temperature warning.
[23]
Remote, ready,
no thermal
warning
Adjustable frequency drive is ready for
operation and is in [Auto on] mode.
There is no over-temperature warning.
[24]
Ready, voltage
OK
Adjustable frequency drive is ready for
operation and the AC line voltage is
within the specified voltage range (see
General Specifications
section in the
Design Guide).
[25]
Reverse
Reversing. Logic ‘1’
when CW rotation of
the motor. Logic ‘0’ when CCW rotation
of the motor. If the motor is not rotating,
the output will follow the reference.
[26]
Bus OK
Active communication (no timeout) via
the serial communication port.
[27]
Torque limit
and stop
Use in performing a coasting stop and in
torque limit condition. If the Adjustable
frequency drive has received a stop signal
and is at the torque limit, the signal is
Logic ‘0’.
[28]
Brake, no brake
warning
Brake is active and there are no warnings.
[29]
Brake ready, no
fault
Brake is ready for operation and there are
no faults.
[30]
Brake fault
(IGBT)
Output is Logic ‘1’ when the brake IGBT is
short-circuited. Use this function to
protect the Adjustable frequency drive if
there is a fault on the brake modules. Use
the output/relay to cut out the AC line
voltage from the Adjustable frequency
drive.
[31]
Relay 123
The relay is activated when Control Word
[0] is selected in parameter group 8-**.
[32]
Mechanical
brake control
Enables control of an external mechanical
brake, see description in the section
Control of Mechanical Brake
, and
parameter group 2-2*
[33]
Safe stop
activated (FC
302 only)
Indicates that the safe stop on terminal
37 has been activated.
[40]
Out of ref
range
Active when the actual speed is outside
settings in
4-52 Warning Speed Low
to
4-55 Warning Reference High
.
[41]
Below
reference low
Active when actual speed is below speed
reference setting.
[42]
Above
reference high
Active when actual speed is above speed
reference setting
[43]
Extended PID
Limit
[45]
Bus Ctrl
Controls output via bus. The state of the
output is set in
5-90 Digital & Relay Bus
Control
. The output state is retained in
the event of bus timeout.
[46]
Bus Ctrl On at
timeout
Controls output via bus. The state of the
output is set in
5-90 Digital & Relay Bus
Control
. In the event of a bus timeout,
the output state is set high (On).
Parameter Descriptions