Decrease
or
Clear
. To activate the function, at least one
digital input must be set up to
Increase
or
Decrease
.
3-90 Step Size
Range:
Function:
0.10 %
*
[0.01 - 200.00 %]
3-91 Ramp Time
Range:
Function:
1.00
s
*
[0.00 -
3600.00 s]
Enter the ramp time, i.e., the time for
adjustment of the reference from 0% to
100% of the specified digital potentiometer
function (Increase, Decrease or Clear).
If Increase/Decrease is activated for longer
than the ramp delay period specified in
3-95 Ramp Delay
, the actual reference will be
ramped up/down according to this ramp
time. The ramp time is defined as the time
used to adjust the reference by the step size
specified in
3-90 Step Size
.
3-92 Power Restore
Option: Function:
[0]
*
Off Resets the Digital Potentiometer reference to 0% after
power-up.
[1]
On Restores the most recent Digital Potentiometer
reference at power-up.
3-93 Maximum Limit
Range:
Function:
100 %
*
[-200 - 200
%]
Set the maximum permissible value for
the resultant reference. This is advisable if
3-93 Maximum Limit
Range:
Function:
the Digital Potentiometer is used for fine
tuning of the resulting reference.
3-94 Minimum Limit
Range:
Function:
-100 %
*
[-200 - 200
%]
Set the minimum permissible value for
the resultant reference. This is advisable
if the Digital Potentiometer is used for
fine tuning of the resulting reference.
3-95 Ramp Delay
Range:
Function:
Application
dependent
*
[Application
dependant]
Enter the delay required from
activation of the digital potenti-
ometer function until the
Adjustable frequency drive starts
to ramp the reference. With a
delay of 0 ms, the reference
starts to ramp as soon as
INCREASE/DECREASE is activated.
See also
3-91 Ramp Time
.
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
3-43
3
3