13-41 Logic Rule Operator 1
Array [6]
Option:
Function:
Select the first logical operator to use on
the Boolean inputs from
13-40 Logic Rule
Boolean 1
and
13-42 Logic Rule Boolean 2
.
[13-**] signifies the Boolean input of
parameter group 13-**.
[0]
*
DISABLED
Ignores
13-42 Logic Rule Boolean 2
,
13-43 Logic Rule Operator 2
, and
13-44 Logic
Rule Boolean 3
.
[1]
AND
Evaluates the expression [13-40] AND
[13-42].
[2]
OR
evaluates the expression [13-40] OR [13-42].
[3]
AND NOT
evaluates the expression [13-40] AND NOT
[13-42].
[4]
OR NOT
evaluates the expression [13-40] OR NOT
[13-42].
[5]
NOT AND
evaluates the expression NOT [13-40] AND
[13-42].
[6]
NOT OR
evaluates the expression NOT [13-40] OR
[13-42].
[7]
NOT AND NOT evaluates the expression NOT [13-40] AND
NOT [13-42].
[8]
NOT OR NOT
evaluates the expression NOT [13-40] OR
NOT [13-42].
13-42 Logic Rule Boolean 2
Array [6]
Option:
Function:
[0]
*
False
Select the second Boolean (TRUE
or FALSE) input for the selected
logic rule. See
13-01 Start Event
([0] - [61]) and
13-02 Stop Event
([70] - [75]) for further description.
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
13-42 Logic Rule Boolean 2
Array [6]
Option:
Function:
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[39]
Start command
[40]
Drive stopped
[41]
Reset Trip
[42]
Auto-reset Trip
[43]
Ok key
[44]
Reset key
[45]
Left key
[46]
Right key
[47]
Up key
[48]
Down key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[75]
Start command given
[76]
Digital input x30/2
[77]
Digital input x30/3
[78]
Digital input x30/4
[79]
Digital input x46/1
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
3-121