13-16 RS-FF Operand R
Option:
Function:
[43]
Ok key
[44]
Reset key
[45]
Left key
[46]
Right key
[47]
Up key
[48]
Down key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[75]
Start command given
[76]
Digital input x30/2
[77]
Digital input x30/3
[78]
Digital input x30/4
[79]
Digital input x46/1
[80]
Digital input x46/3
[81]
Digital input x46/5
[82]
Digital input x46/7
[83]
Digital input x46/9
[84]
Digital input x46/11
[85]
Digital input x46/13
[90]
ATEX ETR cur. warning
[91]
ATEX ETR cur. alarm
[92]
ATEX ETR freq. warning
[93]
ATEX ETR freq. alarm
[94]
RS Flipflop 0
[95]
RS Flipflop 1
[96]
RS Flipflop 2
[97]
RS Flipflop 3
[98]
RS Flipflop 4
[99]
RS Flipflop 5
[100]
RS Flipflop 6
[101]
RS Flipflop 7
3.14.5 13-2* Timers
Use the result (TRUE or FALSE) from
timers
directly to
define an
event
(see
13-51 SL Controller Event
), or as
Boolean input in a
logic rule
(see
13-40 Logic Rule Boolean
1
,
13-42 Logic Rule Boolean 2
or
13-44 Logic Rule Boolean 3
).
A timer is only FALSE when started by an action (i.e., Start
timer 1 [29]) until the timer value entered in this
parameter is elapsed. Then it becomes TRUE again.
All parameters in this parameter group are array
parameters with index 0 to 2. Select index 0 to program
Timer 0, select index 1 to program Timer 1, and so on.
13-20 SL Controller Timer
Range:
Function:
Application
dependent
*
[Application
dependant]
Enter the value to define the
duration of the FALSE output
from the programmed timer. A
timer is only FALSE if it is started
by an action (i.e.,
Start timer 1
[29]) and until the given timer
value has elapsed.
3.14.6 13-4* Logic Rules
Combine up to three boolean inputs (TRUE / FALSE inputs)
from timers, comparators, digital inputs, status bits and
events using the logical operators AND, OR, and NOT.
Select Boolean inputs for the calculation in
13-40 Logic Rule
Boolean 1
,
13-42 Logic Rule Boolean 2
and
13-44 Logic Rule
Boolean 3
. Define the operators used to logically combine
the selected inputs in
13-41 Logic Rule Operator 1
and
13-43 Logic Rule Operator 2
.
. . .
. . .
. . .
. . .
Par. LC-43
Logic Rule Operator 2
Par. LC-41
Logic Rule Operator 1
Par. LC-40
Logic Rule Boolean 1
Par. LC-42
Logic Rule Boolean 2
Par. LC-44
Logic Rule Boolean 3
130BB673.10
Priority of calculation
The results of
13-40 Logic Rule Boolean 1
,
13-41 Logic Rule
Operator 1
and
13-42 Logic Rule Boolean 2
are calculated
first. The outcome (TRUE / FALSE) of this calculation is
combined with the settings of
13-43 Logic Rule Operator 2
and
13-44 Logic Rule Boolean 3
, yielding the final result
(TRUE / FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[0]
*
False
Select the first Boolean (TRUE or
FALSE) input for the selected logic
rule.
See
13-01 Start Event
([0] - [61])
and
13-02 Stop Event
([70] - [75])
for further description.
[1]
True
[2]
Running
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
3-119