Unit Type
Speed Relation
Dimensionless
Linear
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure
Quadratic
Power
Cubic
0-30 Unit for User-defined Readout
Option:
Function:
It is possible to program a value to be shown in
the display of the LCP. The value will have a
linear, squared or cubed relation to speed. This
relation will depend on the unit selected (see
table above). The actual calculated value can be
read in
16-09 Custom Readout
, and/or shown in
the display by selecting Custom Readout [16-09]
in
0-20 Display Line 1.1 Small
to
0-24 Display Line 3
Large
.
[0]
*
None
[1]
%
[5]
PPM
[10]
1/min
[11]
rpm
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
0-30 Unit for User-defined Readout
Option:
Function:
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[160] °F
[170] psi
[171] lb/in²
[172] in WG
[173] ft WG
[180] HP
0-31 Min Value of User-defined Readout
Range:
Function:
0.00 Custom-
ReadoutUnit
*
[Application
dependant]
This parameter sets the min.
value of the custom defined
readout (occurs at zero speed).
Only possible to set different
from 0 is when selecting a
linear unit in
0-30 Unit for User-
defined Readout
. For quadratic
and cubic units, the minimum
value will be 0.
0.00 Custom-
ReadoutUnit
*
[Application
dependant]
This parameter sets the min.
value of the custom defined
readout (occurs at zero speed).
Only possible to set different
from 0 is when selecting a
linear unit in
0-30 Unit for User-
defined Readout
. For quadratic
and cubic units, the minimum
value will be 0.
0-32 Custom Readout Max Value
Range:
Function:
100.00 Custom-
ReadoutUnit
*
[ par. 0-31 -
999999.99
CustomRea-
doutUnit]
This parameter sets the max
value to be shown when
the speed of the motor has
reached the set value for
4-13 Motor Speed High Limit
[RPM]
or
4-14 Motor Speed
High Limit [Hz]
(depends on
setting in
0-02 Motor Speed
Unit
).
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
3-9