3-02 Minimum Reference
Range:
Function:
Speed closed-loop
[1], RPM;
for
Torque
[2], Nm.
•
The unit selected in
3-01 Reference/Feedback
Unit
.
3-03 Maximum Reference
Range:
Function:
Application
dependent
*
[Application
dependant]
Enter the maximum reference. The
maximum reference is the highest
value obtainable by adding all
references together.
The Maximum Reference unit
matches:
•
The choice of configu-
ration in
1-00 Configuration
Mode
: for
Speed closed-loop
[1], RPM; for
Torque
[2],
Nm.
•
The unit selected in
3-00 Reference Range
.
3-04 Reference Function
Option:
Function:
[0]
*
Sum
Sums both external and preset reference
sources.
[1]
External/Preset Use either the preset or the external
reference source.
Shift between external and preset via a
command on a digital input.
3.5.2 3-1* References
Select the preset reference(s). Select Preset ref. bit 0 / 1 / 2
[16], [17] or [18] for the corresponding digital inputs in
parameter group 5-1*.
3-10 Preset Reference
Array [8]
Range: 0-7
Range:
Function:
0.00 %
*
[-100.00 - 100.00 %]
Preset ref. bit
2
1
0
Preset ref. 0
0
0
0
Preset ref. 1
0
0
1
Preset ref. 2
0
1
0
Preset ref. 3
0
1
1
Preset ref. 4
1
0
0
Preset ref. 5
1
0
1
Preset ref. 6
1
1
0
Preset ref. 7
1
1
1
3-11 Jog Speed [Hz]
Range:
Function:
Application
dependent
*
[Application
dependant]
The jog speed is a fixed
output speed at which the
Adjustable frequency drive is
running when the jog
function is activated.
See also
3-80 Jog Ramp Time
.
3-12 Catch up/slow Down Value
Range:
Function:
0.00 %
*
[0.00 - 100.00 %]
3-13 Reference Site
Option:
Function:
Select which reference site to activate.
[0]
*
Linked to
Hand / Auto
Use local reference when in hand mode; or
remote reference when in auto mode.
[1]
Remote
Use remote reference in both hand mode
and auto mode.
[2]
Local
Use local reference in both hand mode and
auto mode.
NOTE!
When set to Local [2], the Adjustable
frequency drive will start with this
setting again following a 'power-down'.
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
3-35