10-21 COS Filter 2
Range:
Function:
0
*
[0 - 65535 ] Enter the value for COS Filter 2, to set up the
filter mask for the Main Actual Value. When
operating in COS (Change-Of-State), this
function filters out bits in the Main Actual
Value that should not be sent if they change.
10-22 COS Filter 3
Range:
Function:
0
*
[0 - 65535 ] Enter the value for COS Filter 3, to set up the
filter mask for PCD 3. When operating in COS
(Change-Of-State), this function filters out bits
in PCD 3 that should not be sent if they
change.
10-23 COS Filter 4
Range:
Function:
0
*
[0 - 65535 ] Enter the value for COS Filter 4 to set up the
filter mask for PCD 4. When operating in COS
(Change-Of-State), this function filters out bits
in PCD 4 that should not be sent if they
change.
3.12.4 10-3* Parameter Access
Parameter group providing access to indexed parameters
and defining programming set-up.
10-30 Array Index
Range:
Function:
0
*
[0 - 255 ] View array parameters. This parameter is valid
only when a DeviceNet serial communication bus
is installed.
10-31 Store Data Values
Option:
Function:
Parameter values changed via DeviceNet are
not automatically stored in non-volatile
memory. Use this parameter to activate a
function that stores parameter values in the
EEPROM non-volatile memory, so that changed
parameter values will be retained at power-
down.
[0]
*
Off
Deactivates the non-volatile storage function.
[1]
Store all
setups
Stores all parameter values from the active set-
up in the non-volatile memory. The selection
returns to Off [0] when all values have been
stored.
[2]
Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
10-31 Store Data Values
Option:
Function:
Off
[0] when all parameter values have been
stored.
10-32 Devicenet Revision
Range:
Function:
Application
dependent
*
[0 - 65535 ] View the DeviceNet revision
number. This parameter is used
for EDS file creation.
Application
dependent
*
[0 - 65535 ] View the DeviceNet revision
number. This parameter is used
for EDS file creation.
10-33 Store Always
Option: Function:
[0]
*
Off Deactivates non-volatile storage of data.
[1]
On Stores parameter data received via DeviceNet in
EEProm non-volatile memory as default.
10-39 Devicenet F Parameters
Array [1000]
No LCP access
Range:
Function:
0
*
[0 - 0 ] This parameter is used to configure the Adjustable
frequency drive via DeviceNet and build the EDS
file.
Parameter Descriptions
FC 300 Programming Guide
3-104
MG33MD22 - VLT
®
is a registered Danfoss trademark
3
3