3.18 Parameters: 17-** Motor Feedb.
Option
Additional parameters to configure the Encoder (MCB 102)
or the Resolver (MCB 103) Feedback Option.
3.18.1 17-1* Inc. Enc. Interface
Parameters in this group configure the incremental
interface of the MCB 102 option. Note that both the
incremental and absolute interfaces are active at the same
time.
NOTE!
These parameters cannot be adjusted while the motor is
running.
17-10 Signal Type
Select the incremental type (A/B channel) of the encoder in use.
Find the information on the encoder data sheet.
Select
None
[0] if the feedback sensor is an absolute encoder
only.
Option:
Function:
[0]
None
[1]
*
RS422 (5V TTL)
[2]
Sinusoidal 1Vpp
17-11 Resolution (PPR)
Range:
Function:
1024
*
[10 - 10000 ]
3.18.2 17-2* Abs. Enc. Interface
Parameters in this group configure the absolute interface
of the MCB 102 option. Note that both the incremental
and absolute interfaces are active at the same time.
17-20 Protocol Selection
Select HIPERFACE [1] if the encoder is absolute only.
Select None [0] if the feedback sensor is an incremental encoder
only.
Option:
Function:
[0]
*
None
[1]
HIPERFACE
[2]
EnDat
[4]
SSI
NOTE!
This parameter cannot be adjusted while the motor is
running.
17-21 Resolution (Positions/Rev)
Select the resolution of the absolute encoder, i.e., the number of
counts per revolution.
The value depends on setting in
17-20 Protocol Selection
.
Range:
Function:
Application
dependent
*
[Application
dependant]
NOTE!
This parameter cannot be adjusted while the motor is
running.
17-24 SSI Data Length
Range:
Function:
13
*
[13 - 25 ] Set the number of bits for the SSI message.
Choose 13 bits for single-turn encoders and 25
bits for multi-turn encoder.
17-25 Clock Rate
Range:
Function:
Application
dependent
*
[Application
dependant]
Set the SSI clock rate. With
long encoder cables the
clock rate must be reduced.
17-26 SSI Data Format
Option:
Function:
[0]
*
Gray code
[1]
Binary code Set the data format of the SSI data. Choose
between Gray or Binary format.
17-34 HIPERFACE Baudrate
Select the baud rate of the attached encoder.
The parameter is only accessible when
17-20 Protocol Selection
is
set to HIPERFACE [1].
Option:
Function:
[0]
600
[1]
1200
[2]
2400
[3]
4800
[4]
*
9600
[5]
19200
[6]
38400
NOTE!
This parameter cannot be adjusted while the motor is
running.
3.18.3 17-5* Resolver Interface
Parameter group 17-5* is used for setting parameters for
the MCB 103 resolver option.
Parameter Descriptions
FC 300 Programming Guide
3-148
MG33MD22 - VLT
®
is a registered Danfoss trademark
3
3