NOTE!
This parameter cannot be adjusted while the motor is
running.
NOTE!
Max. output frequency cannot exceed 10% of the inverter
switching frequency (
14-01 Switching Frequency
).
4-20 Torque Limit Factor Source
Option:
Function:
Select an analog input for scaling the
settings in
4-16 Torque Limit Motor
Mode
and
4-17 Torque Limit Generator
Mode
from 0% to 100% (or inverse).
The signal levels corresponding to
0% and 100% are defined in the
analog input scaling, e.g., parameter
group 6-1*. This parameter is only
active when
1-00 Configuration Mode
is in
Speed Open-loop
or
Speed
Closed-loop
.
[0]
*
No function
[2]
Analog in 53
[4]
Analog in 53 inv
[6]
Analog in 54
[8]
Analog in 54 inv
[10] Analog in X30-11
[12] Analog in X30-11
inv
[14] Analog in X30-12
[16] Analog in X30-12
inv
4-21 Speed Limit Factor Source Option
Option:
Function:
Select an analog input for scaling
the settings in
4-19 Max Output
Frequency
from 0% to 100% (or vice
versa). The signal levels
corresponding to 0% and 100% are
defined in the analog input scaling,
e.g., parameter group 6-1*. This
parameter is only active when
1-00 Configuration Mode
is in
Torque
Mode
.
[0]
*
No function
[2]
Analog input 53
[4]
Analog input 53 inv
[6]
Analog input 54
[8]
Analog input 54 inv
[10] Analog input X30-11
[12] Analog input X30-11
inv
4-21 Speed Limit Factor Source Option
Option:
Function:
[14] Analog input X30-12
[16] Analog input X30-12
inv
3.6.2 4-3* Motor Feedback Monitoring
The parameter group includes monitoring and handling of
motor feedback devices such as encoders, resolvers, etc.
4-30 Motor Feedback Loss Function
Option:
Function:
Select which reaction the Adjustable
frequency drive should take if a
feedback fault is detected. The
selected action is to take place when
the feedback signal differs from the
output speed where its range is
specified in
4-31 Motor Feedback
Speed Error
during its time frame set
in
4-32 Motor Feedback Loss Timeout
.
[0]
Disabled
[1]
Warning
[2]
*
Trip
[3]
Jog
[4]
Freeze Output
[5]
Max Speed
[6]
Switch to Open Loop
[7]
Select Setup 1
[8]
Select Setup 2
[9]
Select Setup 3
[10] Select Setup 4
[11] stop & trip
Warning/Alarm 61 Feedback Error is related to the Motor
Feedback Loss Function.
4-31 Motor Feedback Speed Error
Range:
Function:
300 RPM
*
[1 - 600 RPM] Select the max. allowed tracking error
in speed from the calculated and the
actual mechanical shaft output
speeds.
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®