16-37 Inv. Max. Current
Range:
Function:
connected motor. The data are
used for calculation of torque,
motor protection, etc.
Application
dependent
*
[0.01 -
10000.00 A]
View the inverter maximum
current, which should match the
nameplate data on the
connected motor. The data are
used for calculation of torque,
motor protection, etc.
16-38 SL Controller State
Range:
Function:
0
*
[0 - 100 ] View the state of the event under execution by
the SL controller.
16-39 Control Card Temp.
Range:
Function:
0 °C
*
[0 - 100 °C]
16-40 Logging Buffer Full
Option: Function:
View whether the logging buffer is full (see parameter
group 15-1*). The logging buffer will never be full
when
15-13 Logging Mode
is set to
Log always
[0].
[0]
*
No
[1]
Yes
16-49 Current Fault Source
Range:
Function:
0
*
[0 - 8 ] Value indicates source of current faults including
short circuit, overcurrent, and phase imbalance
(from left):
1-4 Inverter
5-8 Rectifier
0 No fault recorded
3.17.3 16-5* Ref. & Feedb.
16-50 External Reference
Range:
Function:
0.0
*
[-200.0 -
200.0 ]
View the total reference, the sum of
digital, analog, preset, bus and freeze
references, plus catch-up and slow-down.
16-51 Pulse Reference
Range:
Function:
0.0
*
[-200.0 -
200.0 ]
View the reference value from
programmed digital input(s). The readout
16-51 Pulse Reference
Range:
Function:
can also reflect the impulses from an
incremental encoder.
16-52 Feedback [Unit]
Range:
Function:
0.000 Reference-
FeedbackUnit
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
View the feedback unit
resulting from the
selection of unit and
scaling in
3-00 Reference
Range
,
3-01 Reference/
Feedback Unit
,
3-02 Minimum Reference
and
3-03 Maximum
Reference
.
16-53 Digi Pot Reference
Range:
Function:
0.00
*
[-200.00 - 200.00 ] View the contribution of the digital
potentiometer to the actual reference.
16-57 Feedback [RPM]
Range:
Function:
0 RPM
*
[-30000 -
30000 RPM]
Readout parameter where the actual
motor RPM from the feedback source
can be read in both closed-loop and
open-loop. The feedback source is
selected by
7-00 Speed PID Feedback
Source
.