13-02 Stop Event
Select the Boolean (TRUE or FALSE) input to activate Smart Logic
Control.
Option:
Function:
[73]
SL Time-out 6
SL- Timeout 6
[73] Smart Logic
Controller timer 6 is timed out.
[74]
SL Time-out 7
SL Timeout 7
[74] Smart Logic
Controller timer 7 is timed out.
[75]
Start command given
[76]
Digital input x30/2
[77]
Digital input x30/3
[78]
Digital input x30/4
[79]
Digital input x46/1
[80]
Digital input x46/3
[81]
Digital input x46/5
[82]
Digital input x46/7
[83]
Digital input x46/9
[84]
Digital input x46/11
[85]
Digital input x46/13
[90]
ATEX ETR cur. warning Selectable if
1-90 Motor Thermal
Protection
is set to [20] or [21]. If
the alarm 164 ATEX ETR
cur.lim.alarm is active, the output
will be 1.
[91]
ATEX ETR cur. alarm
Selectable if
1-90 Motor Thermal
Protection
is set to [20] or [21]. If
the alarm 166 ATEX ETR
freq.lim.alarm is active, the output
will be 1.
[92]
ATEX ETR freq. warning Selectable if
1-90 Motor Thermal
Protection
is set to [20] or [21]. If
the alarm 163 ATEX ETR
cur.lim.warning is active, the
output will be 1.
[93]
ATEX ETR freq. alarm
Selectable if
1-90 Motor Thermal
Protection
is set to [20] or [21]. If
the warning 165 ATEX ETR
freq.lim.warning is active, the
output will be 1.
[94]
RS Flipflop 0
[95]
RS Flipflop 1
[96]
RS Flipflop 2
[97]
RS Flipflop 3
[98]
RS Flipflop 4
[99]
RS Flipflop 5
[100] RS Flipflop 6
[101] RS Flipflop 7
13-03 Reset SLC
Option:
Function:
[0]
*
Do not reset
SLC
Retains programmed settings in all group
13 parameters (13-**).
[1]
Reset SLC
Resets all group 13 parameters (13-**) to
default settings.
3.14.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e., output frequency, output current, analog input, etc.)
to fixed preset values.
Par. LC-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. LC-10
Comparator Operand
Par. LC-12
Comparator Value
130BB672.10
In addition, there are digital values that will be compared
to fixed time values. See explanation in
13-10 Comparator
Operand
. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 to program Comparator 0,
select index 1 to program Comparator 1, etc.
13-10 Comparator Operand
Array [6]
Option:
Function:
Choices [1] to [31] are variables that will
be compared based on their values.
Choices [50] to [186] are digital values
(TRUE/FALSE) where the comparison is
based on the amount of time during
which they are set to TRUE or FALSE,
respectively. See
13-11 Comparator
Operator
.
Select the variable to be monitored by
the comparator.
[0]
*
DISABLED
DISABLED
[0] The comparator is
disabled.
[1]
Reference
Reference
[1] The resulting remote
reference (not local) as a percentage.
[2]
Feedback
Feedback
[2] In the unit [RPM] or [Hz]
[3]
Motor speed
Motor speed
[3] [RPM] or [Hz]
[4]
Motor current
Motor current
[4] [A]
[5]
Motor torque
Motor torque
[5] [Nm]
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®
is a registered Danfoss trademark
3-113