13-01 Start Event
Option:
Function:
[4]
On reference
On reference
[4] The motor is running
on reference.
[5]
Torque limit
Torque limit
[5] The torque limit, set in
4-16 Torque Limit Motor Mode
or
4-17 Torque Limit Generator Mode
, has
been exceeded.
[6]
Current limit
Current limit
[6] The motor current
limit, set in
4-18 Current Limit
, has been
exceeded.
[7]
Out of current
range
Out of current range
[7] The motor
current is outside the range set in
4-18 Current Limit
.
[8]
Below I low
Below I low
[8] The motor current is
lower than set in
4-50 Warning Current
Low
.
[9]
Above I high
Above I high
[9] The motor current is
higher than set in
4-51 Warning Current
High
.
[10]
Out of speed
range
Out of speed range
[10] The speed is
outside the range set in
4-52 Warning
Speed Low
and
4-53 Warning Speed
High
.
[11]
Below speed low
Below speed low
[11] The output speed
is lower than the setting in
4-52 Warning Speed Low
.
[12]
Above speed
high
Above speed high
[12] The output
speed is higher than the setting in
4-53 Warning Speed High
.
[13]
Out of feedb.
range
Out of feedb. Range
[13] The feedback
is outside the range set in
4-56 Warning Feedback Low
and
4-57 Warning Feedback High
.
[14]
Below feedb. low
Below feedb. Low
[14] The feedback is
below the limit set in
4-56 Warning
Feedback Low
.
[15]
Above feedb.
high
Above feedb. High
[15] The feedback is
above the limit set in
4-57 Warning
Feedback High
.
[16]
Thermal warning
Thermal warning
[16] The thermal
warning turns on when the
temperature exceeds the limit in the
motor, the Adjustable frequency drive,
the brake resistor or the thermistor.
[17]
Mains out of
range
Mains out of range
[17] The AC line
voltage is outside the specified voltage
range.
13-01 Start Event
Option:
Function:
[18]
Reversing
Reverse
[18] The output is high when
the Adjustable frequency drive is
running counter clockwise (the logical
product of the status bits “running”
AND “reverse”).
[19]
Warning
Warning
[19] A warning is active.
[20]
Alarm (trip)
Alarm (trip)
[20] A (trip) alarm is active.
[21]
Alarm (trip lock)
Alarm (trip lock)
[21] A (Trip lock) alarm
is active.
[22]
Comparator 0
Comparator 0
[22] Use the result of
comparator 0.
[23]
Comparator 1
Comparator 1
[23] Use the result of
comparator 1.
[24]
Comparator 2
Comparator 2
[24] Use the result of
comparator 2.
[25]
Comparator 3
Comparator 3
[25] Use the result of
comparator 3.
[26]
Logic rule 0
Logic rule 0
[26] Use the result of logic
rule 0.
[27]
Logic rule 1
Logic rule 1
[27] Use the result of logic
rule 1.
[28]
Logic rule 2
Logic rule 2
[28] Use the result of logic
rule 2.
[29]
Logic rule 3
Logic rule 3
[29] Use the result of logic
rule 3.
[33]
Digital input DI18
Digital input DI18
[33] Use the result of
digital input 18.
[34]
Digital input DI19
Digital input DI19
[34] Use the result of
digital input 19.
[35]
Digital input DI27
Digital input DI27
[35] Use the result of
digital input 27.
[36]
Digital input DI29
Digital input DI27
[35] Use the result of
digital input 29.
[37]
Digital input DI32
Digital input DI32
[37] Use the result of
digital input 32.
[38]
Digital input DI33
Digital input DI33
[38] Use the result of
digital input 33.
[39]
Start command
Start command
[39] A start command is
issued.
[40]
Drive stopped
Drive stopped
[40] A stop command
(Jog, Stop, Qstop, Coast) is issued –
and not from the SLC itself.
[41]
Reset Trip
Reset Trip
[41] A reset is issued
Parameter Descriptions
FC 300 Programming Guide
MG33MD22 - VLT
®