14-56 Capacitance Output Filter
Compensation function of the LC filter requires the per phase
equivalent star connected capacitance of the filter (3 times the
capacity between two phases when capacitance is ’Delta’
connection).
Range:
Function:
NOTE!
This is required for
correct compensation
in flux mode
(
1-01 Motor Control
Principle
)
Application
dependent
*
[0.1 - 6500.0
uF]
14-57 Inductance Output Filter
Range:
Function:
Application
dependent
*
[0.001 -
65.000 mH]
Application
dependent
*
[0.001 -
65.000 mH]
Set the inductance of the
output filter. The value can be
found on the filter label.
NOTE!
This is required for correct
compensation in flux mode
(
1-01 Motor Control
Principle
)
3.15.6 14-7* Compatibility
The parameters in this group are for setting of compati-
bility for VLT 3000, VLT 5000 to FC 300.
14-72 VLT Alarm Word
Option:
Function:
[0] 0–4294967295 Read out the alarm word corresponding to
VLT 5000.
14-73 VLT Warning Word
Option:
Function:
[0] 0–4294967295 Read out the warning word corresponding to
VLT 5000.
14-74 Leg. Ext. Status Word
Range:
Function:
0
*
[0 - 4294967295 ] Read out the ext. status word
corresponding to VLT 5000
3.15.7 14-8* Options
14-80 Option Supplied by External 24VDC
Option: Function:
[0]
No Select No [0] to use the adjustable frequency drive's
24V DC supply.
[1]
*
Yes Select Yes [1] if an external 24V DC supply will be
used to power the option. Inputs/outputs will be
galvanically isolated from the drive when operated
from an external supply.
NOTE!
This parameter is only changing function by performing a
power cycle.
14-89 Option Detection
Selects the behavior of the Adjustable frequency drive when a
change in the option configuration is detected.
Option:
Function:
[0]
*
Protect Option
Config.
Freezes the current settings and
prevents unwanted changes when
missing or defective options are
detected.
[1]
Enable Option
Change
Changes drive settings and is used
when modifying the system configu-
ration. This parameter setting will
return to [0] after an option change.
14-90 Fault Level
Option:
Function:
[0]
*
Off
Use this parameter to customize fault levels. Use
[0] "Off" with caution as it will ignore all
warnings and alarms for the chosen source.
[1]
Warning
[2]
Trip
[3]
Trip Lock
Parameter Descriptions
FC 300 Programming Guide
3-134