2.8.7. 5-6* Pulse Outputs
Parameters for configuring the scaling and output functions of pulse outputs. The pulse outputs are designated to terminals 27 or 29. Select terminal 27
output in par. 5-01 and terminal 29 output in par. 5-02.
Options for readout output variables:
Parameters for configuring the scaling and output functions of pulse outputs. The pulse outputs are designated
to terminals 27 or 29. Select terminal 27 output in par. 5-01 and terminal 29 output in par. 5-02.
[0]
*
No operation
[45]
Bus control
[48]
Bus control time-out
[51]
MCO controlled
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque relative to limit
[105]
Torque relative to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
5-60 Terminal 27 Pulse Output Variable
Option:
Function:
[0]
No operation
Select the variable for viewing on the terminal 27 display.
This parameter cannot be adjusted while the motor is running.
5-62 Pulse Output Maximum Frequency #27
Range:
Function:
5000 Hz
*
[0 - 32000 Hz]
Set the maximum frequency for terminal 27, corresponding to the output variable selected in par. 5-60.
This parameter cannot be adjusted while the motor is running.
5-63 Terminal 29 Pulse Output Variable
Option:
Function:
[0]
*
No operation
Select the variable for viewing on the terminal 29 display. This parameter is available for FC 302 only.
This parameter cannot be adjusted while the motor is running.