Select the control source in Instance 21/71 and 20-70.
[0]
*
Off
Enables control via analog/digital inputs.
[1]
On
enable control via the fieldbus.
2.13.4. 10-2* COS Filters
Parameters for configuring COS filter settings.
10-20 COS Filter 1
Range:
Function:
0000
*
[0 - FFFF]
Enter the value for COS Filter 1 to set up the filter mask for the Status Word. When operating in COS (Change-
Of-State), this function filters out bits in the Status Word that should not be sent if they change.
10-21 COS Filter 2
Range:
Function:
0000
*
[0 - FFFF]
Enter the value for COS Filter 2, to set up the filter mask for the Main Actual Value. When operating in COS
(Change-Of-State), this function filters out bits in the Main Actual Value that should not be sent if they change.
10-22 COS Filter 3
Range:
Function:
0000
*
[0 - FFFF]
Enter the value for COS Filter 3, to set up the filter mask for PCD 3. When operating in COS (Change-Of-State),
this function filters out bits in PCD 3 that should not be sent if they change.
10-23 COS Filter 4
Range:
Function:
0000
*
[0 - FFFF]
Enter the value for COS Filter 4 to set up the filter mask for PCD 4. When operating in COS (Change-Of-State),
this function filters out bits in PCD 4 that should not be sent if they change.
2.13.5. 10-3* Parameter Access
Parameter group providing access to indexed parameters and defining programming set-up.
10-30 Array Index
Range:
Function:
0
*
[0 - 255]
Read only from LCP.
View array parameters. This parameter is valid only when a DeviceNet fieldbus is installed.
10-31 Store Data Values
Option:
Function:
Parameter values changed via DeviceNet are not automatically stored in non-volatile memory. Use this param-
eter to activate a function that stores parameter values in the EEPROM non-volatile memory, so changed
parameter values will be retained at power-down.
[0]
*
Off
Deactivates the non-volatile storage function.
[1]
Store edit setup
Stores all parameter values from the active set-up in the non-volatile memory. The selection returns to Off [0]
when all values have been stored.
[2]
Store all setups
store all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all
parameter values have been stored.
10-32 Devicenet Revision
Option:
Function:
Major revision
Minor revision
View the DeviceNet revision number. This parameter is used for EDS file creation.