15-07 Reset Running Hours Counter
Option:
Function:
[0]
*
Do not reset
[1]
Reset counter
Select
Reset
[1] and press [OK] to reset the Running Hours counter to zero (see par. 15-01). This parameter
cannot be selected via the serial port, RS 485.
Select
Do not reset
[0] if no reset of the Running Hours counter is desired.
2.16.3. Data Log Settings, 15-1*
The Data Log enables continuous logging of up to 4 data sources (par. 15-10) at individual rates (par. 15-11). A trigger event (par. 15-12) and window
(par. 15-14) are used to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
None
14-72 VLT Alarm Word
14-73 VLT Warning
Word
14-74 VLT Ext. Status
Word
[16-00 Con-
trol Word]
16-01 Reference [Unit]
16-02 Reference %
16-03 Status Word
16-10 Power [kW]
16-11 Power [hp]
16-12 Motor Voltage
16-13 Frequency
16-14 Motor Current
16-16 Torque
16-17 Speed [RPM]
16-18 Motor Thermal
16-30 DC Link Voltage
16-32 Brake Energy / s
16-33 Brake Energy / 2
min
16-34 Heatsink Temp.
16-35 Inverter Thermal
16-50 External Refer-
ence
16-51 Pulse Reference
16-52 Feedback [Unit]
16-54 Feedback 1
[Unit]
16-55 Feedback 2
[Unit]
FC 300 Programming Guide
2. How to Programme