[47]
Up key
[48]
Down key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
Select the first boolean (TRUE or FALSE) input for the selected logic rule.
See par. 13-01
Start Event
([0] - [61]) and par. 13-02
Stop Event
([70] - [74]) for further description.
13-41 Logic Rule Operator 1
Array [6]
Select the first logical operator to use on the Boolean inputs from par. 13-40 and 13-42.
[13 -XX] signifies the boolean input of par. 13-*.
[0]
*
DISABLED
Ignores par. 13-42, 13-43, and 13-44.
[1]
AND
evaluates the expression [13-40] AND [13-42].
[2]
OR
evaluates the expression [13-40] OR [13-42].
[3]
AND NOT
evaluates the expression [13-40] AND NOT [13-42].
[4]
OR NOT
evaluates the expression [13-40] OR NOT [13-42].
[5]
NOT AND
evaluates the expression NOT [13-40] AND [13-42].
[6]
Not or
evaluates the expression NOT [13-40] OR [13-42].
[7]
Not and not
evaluates the expression NOT [13-40] AND NOT [13-42].
[8]
Not or not
evaluates the expression NOT [13-40] OR NOT [13-42].
13-42 Logic Rule Boolean 2
Array [6]
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
FC 300 Programming Guide
2. How to Programme
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark
135
2