Array [1000]
Read only
This parameter contains a list of signals available for selection in par. 9-15 and 9-16.
9-27 Parameter Edit
Option:
Function:
Parameters can be edited via Profibus, the standard RS485 interface, or the LCP.
[0]
Disabled
Disables editing via Profibus.
[1]
*
Enabled
Enables editing via Profibus.
9-28 Process Control
Option:
Function:
Process control (setting of Control Word, speed reference, and process data) is possible via either Profibus or
standard fieldbus but not both simultaneously. Local control is always possible via the LCP. Control via process
control is possible via either terminals or fieldbus depending on the settings in par. 8-50 to 8-56.
[0]
Disable
Disables process control via Profibus, and enables process control via standard fieldbus or Profibus Master class
2.
[1]
*
Enable cyclic master
Enables process control via Profibus Master Class 1, and disables process control via standard fieldbus or Profibus
Master class 2.
9-44 Fault Message Counter
Range:
Function:
0
*
[0-65535]
This parameter displays the number of error events stored in par. 9-45 and 9-47. The maximum buffer capacity
is eight error events. The buffer and counter are set to 0 upon reset or power-up.
9-45 Fault Code
Range:
Function:
0
*
[0 - 0]
This buffer contains the alarm word for all alarms and warnings that have occurred since last reset or power-up.
The maximum buffer capacity is eight error events.
9-47 Fault Number
Range:
Function:
0
*
[0 - 0]
This buffer contains the alarm number (e.g. 2 for live zero error, 4 for mains phase loss) for all alarms and
warnings that have occurred since last reset or power-up. The maximum buffer capacity is eight error events.
9-52 Fault Situation Counter
Range:
Function:
0
*
[0 - 1000]
This parameter displays the number of error events which have occurred since last reset of power-up.
9-53 Profibus Warning Word
This parameter displays Profibus communication warnings. Please refer to the
Profibus Operating Instructions
for
further information.
Read only
FC 300 Programming Guide
2. How to Programme
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark
115
2