[1610]
Power [kW]
Actual power consumed by the motor in kW.
[1611]
Power [hp]
Actual power consumed by the motor in HP.
[1612]
Motor Voltage
Voltage supplied to the motor.
[1613]
Frequency
Motor frequency, i.e. the output frequency from the frequency converter in Hz
[1614]
Motor Current
Phase current of the motor measured as effective value.
[1615]
Frequency [%]
Motor frequency, i.e. the output frequency from the frequency converter in percent.
[1616]
Torque
Present motor load as a percentage of the rated motor torque.
[1617]
*
Speed [RPM]
Speed in RPM (revolutions per minute) i.e. the motor shaft speed in closed loop.
[1618]
Motor Thermal
Thermal load on the motor, calculated by the ETR function.
[1619]
KTY Sensor Tempera-
ture
[1620]
Motor Angle
[1621]
Phase Angle
[1622]
Torque %
[1630]
DC Link Voltage
Intermediate circuit voltage in the frequency converter.
[1632]
BrakeEnergy/s
Present brake power transferred to an external brake resistor.
Stated as an instantaneous value.
[1633]
BrakeEnergy/2 min
Brake power transferred to an external brake resistor. The mean power is calculated continuously for the most
recent 120 seconds.
[1634]
Heatsink Temp.
Present heat sink temperature of the frequency converter. The cut-out limit is 95 ±5 oC; cutting back in occurs
at 70 ±5° C.
[1635]
Inverter Thermal
Percentage load of the inverters.
[1636]
Inv. Nom. Current
Nominal current of the frequency converter.
[1637]
Inv. Max. Current
Maximum current of the frequency converter.
[1638]
SL Control State
State of the event executed by the control.
[1639]
Control Card Temp.
Temperature of the control card.
[1650]
External Reference
Sum of the external reference as a percentage, i.e. the sum of analog/pulse/bus.
[1651]
Pulse Reference
Frequency in Hz connected to the digital inputs (18, 19 or 32, 33).
[1652]
Feedback [Unit]
Reference value from programmed digital input(s).
[1653]
Digi Pot Reference
[1660]
Digital Input
Signal states form the 6 digital terminals (18, 19, 27, 29, 32 and 33). Input 18 corresponds to the bit at the far
left. Signal low = 0; Signal high = 1.
[1661]
Terminal 53 Switch
Setting
Setting of input terminal 54. Current = 0; Voltage = 1.
[1662]
Analog Input 53
Actual value at input 53 either as a reference or protection value.
[1663]
Terminal 54 Switch
Setting
Setting of input terminal 54. Current = 0; Voltage = 1.
[1664]
Analog Input 54
Actual value at input 54 either as reference or protection value.
[1665]
Analog Output 42 [mA] Actual value at output 42 in mA. Use par. 6-50 to select the value to be shown.
[1666]
Digital Output [bin]
Binary value of all digital outputs.
[1667]
Freq. Input #29 [Hz]
Actual value of the frequency applied at terminal 29 as an impulse input.
[1668]
Freq. Input #33 [Hz]
Actual value of the frequency applied at terminal 33 as an impulse input.
[1669]
Pulse Output #27 [Hz] Actual value of impulses applied to terminal 27 in digital output mode.
[1670]
Pulse Output #29 [Hz] Actual value of impulses applied to terminal 29 in digital output mode.
[1671]
Relay Output [bin]
[1672]
Counter A
[1673]
Counter B
[1674]
Prec. Stop Counter
FC 300 Programming Guide
2. How to Programme
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark
31