2.1.8. Initial Commissioning
The easiest way of carrying out the initial commissioning is by using the Quick Menu button and follow the quick set-up procedure using LCP 102 (read
table from left to right):
Press
Q2 Quick Menu
0-01 Language
Set language
1-20 Motor power
Set Motor nameplate power
1-22 Motor voltage
Set Nameplate voltage
1-23 Motor frequency
Set Nameplate frequency
1-24 Motor current
Set Nameplate current
1-25 Motor nominal speed
Set Nameplate speed in RPM
5-12 Terminal 27 Digital Input
If terminal default is
Coast inverse
it is possible to change this
setting to
No function
. No connection to terminal 27 is then
needed for running AMA
1-29 Automatic Motor Adaptation
Set desired AMA function. Enable complete AMA is recommen-
ded
3-02 Minimum reference
Set the minimum speed of the motor shaft
3-03 Maximum reference
Set the maximum speed of the motor shaft
3-41 Ramp1 up time
Set the ramping up time with reference to nominal motor speed
(set in par. 1-25)
3-42 Ramp1 down time
Set the ramping down time with reference to nominal motor
speed (set in par. 1-25)
3-13 Reference site
Set the site from where the reference must work