1-95 KTY Sensor Type
Option:
Function:
Select the used type of KTY sensor:
KTY Sensor type 1: 1Kohm at 100 degrees C
KTY Sensor type 2: 1Kohm at 25 degrees C
KTY Sensor type 3: 2Kohm at 25 degrees C
This parameter only applies for FC 302.
[0]
*
KTY Sensor 1
[1]
KTY Sensor 2
[2]
KTY Sensor 3
1-96 KTY Thermistor Source
Option:
Function:
Selecting analog input terminal 54 to be used as KTY sensor input. Terminal 54 cannot be selected as KTY source
if otherwise used as reference (see par. 3-15 to 3-17).
This parameter only applies for FC 302.
NB!
Connection of KTY-sensor between term. 54 and 55 (GND). See picture in section
KTY Sensor
Connection
.
[0]
*
None
[2]
Analog input 54
1-97 KTY Threshold level
Range:
Function:
80° C [-40 - 140° C]
Select the KTY sensor threshold level for motor thermal protection.
This parameter only applies for FC 302.
2.5. Parameters: Brakes
2.5.1. 2-** Brakes
Parameter group for setting brake features in the frequency converter.
2.5.2. 2-0* DC-Brakes
Parameter group for configuring the DC brake and DC hold functions.
2-00 DC Hold Current
Range:
Function:
50 %
*
[0 - 160%]
Enter a value for holding current as a percentage of the rated motor current I
M,N
set in par. 1-24 Motor Current.
100% DC holding current corresponds to I
M,N
.
This parameter holds the motor function (holding torque) or pre-heats the motor.
This parameter is active if
DC hold
is selected in par. 1-72
Start Function
[0] or par. 1-80
Function at Stop
[1].
NB!
The maximum value depends on the rated motor current.
NB!
Avoid 100 % current for too long. It may damage the motor.