[46]
Bus Ctrl On at timeout
[47]
Bus Ctrl Off at timeout
[51]
MCO controlled
[55]
Pulse output
[60]
Comparator 0
See par. group 13-1*. If Comparator 0 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[61]
Comparator 1
See par. group 13-1*. If Comparator 1 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[62]
Comparator 2
See par. group 13-1*. If Comparator 2 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[63]
Comparator 3
See par. group 13-1*. If Comparator 3 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[64]
Comparator 4
See par. group 13-1*. If Comparator 4 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[65]
Comparator 5
See par. group 13-1*. If Comparator 5 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[70]
Logic Rule 0
See par. group 13-4*. If Logic Rule 0 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[71]
Logic Rule 1
See par. group 13-4*. If Logic Rule 1 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[72]
Logic Rule 2
See par. group 13-4*. If Logic Rule 2 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[73]
Logic Rule 3
See par. group 13-4*. If Logic Rule 3 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[74]
Logic Rule 4
See par. group 13-4*. If Logic Rule 4 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[75]
Logic Rule 5
See par. group 13-4*. If Logic Rule 5 is evaluated as TRUE, the output will go high. Otherwise, it will be low.
[80]
SL Digital Output A
See par. 13-52
SL Control Action
. The output will go high whenever the Smart Logic Action [38]
Set dig. out. A
high
is executed. The output will go low whenever the Smart Logic Action [32] Set dig. out. A low is executed.
[81]
SL Digital Output B
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [39]
Set dig. out. A
high
is executed. The input will go low whenever the Smart Logic Action [33]
Set dig. out. A low
is executed.
[82]
SL Digital Output C
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [40]
Set dig. out. A
high
is executed. The input will go low whenever the Smart Logic Action [34]
Set dig. out. A low
is executed.
[83]
SL Digital Output D
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [41]
Set dig. out. A
high is executed. The input will go low whenever the Smart Logic Action [35]
Set dig. out. A low
is executed.
[84]
SL Digital Output E
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [42]
Set dig. out. A
high
is executed. The input will go low whenever the Smart Logic Action [36]
Set dig. out. A low
is executed.
[85]
SL Digital Output F
See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [43]
Set dig. out. A
high
is executed. The input will go low whenever the Smart Logic Action [37]
Set dig. out. A low
is executed.
[120]
Local reference active
Output is high when par. 3-13
Reference Site
= [2] Local or when par. 3-13
Reference Site
= [0]
Linked to hand
auto
at the same time as the LCP is in Hand on mode.
[121]
Remote reference ac-
tive
Output is high when par. 3-13
Reference Site = Remote
[1] or
Linked to hand/auto
[0] while the LCP is in [Auto
on] mode.
[122]
No alarm
Output is high when no alarm is present.
[123]
Start command active
Output is high when there is an active Start command (i.e. via digital input bus connection or [Hand on] or [Auto
on]), and no Stop or Start command is active.
[124]
Running reverse
Output is high when the frequency converter is running counter clockwise (the logical product of the status bits
‘running’ AND ‘reverse’).
[125]
Drive in hand mode
Output is high when the frequency converter is in Hand on mode (as indicated by the LED light above [Hand
on]).
[126]
Drive in auto mode
Output is high when the frequency converter is in Hand on mode (as indicated by the LED light above [Auto
on]).
5-30 Terminal 27 Digital Output
Option:
Function:
[45]
Bus ctrl.
Controls output via bus. The state of the output is set in par. 5-90. The output state is retained in the event of
bus time-out.
[46]
Bus ctrl. on at timeout Controls output via bus. The state of the output is set in par. 5-90. In the event of bus time-out the output state
is set high (On).
[47]
Bus ctrl. off at timeout Controls output via bus. The state of the output is set in par. 5-90. In the event of bus time-out the output state
is set low (Off).