10-33 Store Always
Option:
Function:
[0]
*
Off
Deactivates non-volatile storage of data.
[1]
On
Stores parameter data received via DeviceNet in EEPROM non-volatile memory as default.
10-39 Devicenet F Parameters
Array [1000]
No LCP access
0
*
[0 - 0]
This parameter is used to configure the frequency converter via DeviceNet and build the EDS-file.
2.14. Parameters: Smart Logic Control
2.14.1. 13-** Prog. Features
Smart Logic Control (SLC) is essentially a sequence of user defined actions (see par. 13-52 [x]) executed by the SLC when the associated user defined
event
(see par. 13-51 [x]) is evaluated as TRUE by the SLC. Events and
actions
are each numbered and linked together in pairs (states). This means that
when
event
[0] is fulfilled (attains the value TRUE),
action
[0] is executed. After this, the conditions of
event
[1] will be evaluated and if evaluated TRUE,
action
[1] will be executed and so on. Only one
event
will be evaluated at any time. If an
event
is evaluated as FALSE, nothing happens (in the SLC)
during the current scan interval and no other
events
will be evaluated. This means that when the SLC starts, it evaluates
event
[0] (and only
event
[0])
each scan interval. Only when
event
[0] is evaluated TRUE, will the SLC execute
action
[0] and start evaluating
event
[1]. It is possible to programme
from 1 to 20
events
and
actions
.
When the last
event
/
action
has been executed, the sequence starts over again from
event
[0] /
action
[0]. The illustration shows an example with three
event / actions:
Starting and stopping the SLC:
Starting and stopping the SLC can be done by selecting .On [1]. or .Off [0]. in par. 13-00. The SLC always starts in state 0 (where it evaluates
event
[0]).
The SLC starts when the Start Event (defined in par. 13-01
Start Event
) is evaluated as TRUE (provided that
On
[1] is selected in par. 13-00). The SLC
stops when the
Stop Event
(par. 13-02) is TRUE. Par. 13-03 resets all SLC parameters and start programming from scratch.
2.14.2. 13-0* SLC Settings
Use the SLC settings to activate, deactivate and reset the Smart Logic Control.
2. How to Programme
FC 300 Programming Guide
126