2.3.7. 0-5* Copy / Save
Copy parameter settings between set-ups and to/from the LCP.
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
[1]
All to LCP
Copies all parameters in all set-ups from the frequency converter memory to the LCP memory.
[2]
All from LCP
Copies all parameters in all set-ups from the LCP memory to the frequency converter memory.
[3]
Size indep. from LCP
copy only the parameters that are independent of the motor size. The latter selection can be used to programme
several frequency converters with the same function without disturbing motor data.
[4]
File from MCO to LCP
[5]
File from LCP to MCO
This parameter cannot be adjusted while the motor is running.
0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function
[1]
Copy to set-up 1
Copies all parameters in the present edit set-up (defined in par. 0-11
Edit Set-up
) to Set-up 1.
[2]
Copy to set-up 2
Copies all parameters in the present edit set-up (defined in par. 0-11
Edit Set-up
) to Set-up 2.
[3]
Copy to set-up 3
Copies all parameters in the present edit set-up (defined in par. 0-11
Edit Set-up
) to Set-up 3.
[4]
Copy to set-up 4
Copies all parameters in the present edit set-up (defined in par. 0-11
Edit Set-up
) to Set-up 4.
[9]
Copy to all
Copies the parameters in the present set-up over to each of the set-ups 1 to 4.
2.3.8. 0-6* Password
Define password access to menus.
0-60 Main Menu Password
Option:
Function:
[100]
*
-9999 - 9999
Define the password for access to the Main Menu via the [Main Menu] key. If par. 0-61
Access to Main Menu
w/o Password
is set to
Full access
[0], this parameter will be ignored.
0-61 Access to Main Menu w/o Password
Option:
Function:
[0]
*
Full access
Disables password defined in par. 0-60
Main Menu Password
.
[1]
Read only
Prevent unauthorized editing of Main Menu parameters.
[2]
No access
Prevent unauthorized viewing and editing of Main Menu parameters.
[3]
Bus: Read only
Read only functions for parameters on fieldbus and/ or FC standard bus.
[4]
Bus: No access
No access to parameters is allowed via fieldbus and/ or FC standard bus.
[5]
All: Read only
Read only function for parameters on LCP, fieldbus or FC standard bus.
[6]
All: No access
No access from LCP, fieldbus or FC standard bus is allowed.
If
Full access
[0] is selected then parameters 0-60, 0-65 and 0-66 will be ignored.
0-65 Quick Menu Password
Range:
Function:
200
*
[-9999 - 9999]
Define the password for access to the Quick Menu via the [Quick Menu] key. If par. 0-66
Access to Quick Menu
w/o Password
is set to
Full access
[0], this parameter will be ignored.