[42]
Auto-reset Trip
[43]
Ok key
[44]
Reset key
[45]
Left key
[46]
Right key
[47]
Up key
[48]
Down key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
Select the boolean (TRUE or FALSE) input to activate Smart Logic Control.
False
[0] enters the fixed value - FALSE.
True
[1] enters the fixed value - TRUE.
Running
[2] The motor is running.
In range
[3] The motor is running within the programmed current and speed ranges set in par. 4-50 to par.
4-53.
On reference
[4] The motor is running on reference.
Torque limit
[5] The torque limit, set in par. 4-16 or 4-17, has been exceeded.
Current limit
[6] The motor current limit, set in par. 4-18, has been exceeded.
Out of current range
[7] The motor current is outside the range set in par. 4-18.
Below I low
[8] The motor current is lower than set in par. 4-50.
Above I high
[9] The motor current is higher than set in par. 4-51.
Out of speed range
[10] The speed is outside the range set in par. 4-52 and 4-53.
Below speed low
[11] The output speed is lower than the setting in par. 4-52.
Above speed high
[12] The output speed is higher than the setting in par. 4-53.
Out of feedb. Range
[13] The feedback is outside the range set in par. 4-56 and 4-57.
Below feedb. Low
[14] The feedback is below the limit set in par. 4-56.
Above feedb. High
[15] The feedback is above the limit set in par. 4-57.
Thermal warning
[16] The thermal warning turns on when the temperature exceeds the limit in the motor, the
frequency converter, the brake resistor or the thermistor.
Mains out of range
[17] The mains voltage is outside the specified voltage range.
Reversing
[18] The output is high when the frequency converter is running counter clockwise (the logical product
of the status bits “running” AND “reverse”).
Warning
[19] A warning is active.
Alarm (trip)
[20] A (trip) alarm is active.
Alarm (trip lock)
[21] A (Trip lock) alarm is active.
Comparator 0
[22] Use the result of comparator 0.
Comparator 1
[23] Use the result of comparator 1.
Comparator 2
[24] Use the result of comparator 2.
Comparator 3
[25] Use the result of comparator 3.
Logic rule 0
[26] Use the result of logic rule 0.
Logic rule 1
[27] Use the result of logic rule 1.
Logic rule 2
[28] Use the result of logic rule 2.
Logic rule 3
[29] Use the result of logic rule 3.
Digital input DI18
[33] Use the result of digital input 18.
Digital input DI19
[34] Use the result of digital input 19.
Digital input DI27
[35] Use the result of digital input 27.
Digital input DI29 FC302Only
[36] Use the result of digital input 29.
Digital input DI32
[37] Use the result of digital input 32.
Digital input DI33
[38] Use the result of digital input 33.
Start command
[39] A start command is issued.
Drive stopped
[40] A stop command ( Jog, Stop, Qstop, Coast) is issued – and not from the SLC itself.
Reset Trip
[41] A reset is issued
Auto-reset Trip
[42] An Auto reset is performed.
OK key
[43] The Ok key is pressed.
Reset key
[44] The reset key is pressed.
2. How to Programme