16-10 Power [kW]
Range:
Function:
0.0kW
*
[0.0 - 1000.0 kW]
View the motor power in kW. The value shown is calculated on the basis of the actual motor voltage and motor
current. The value is filtered, and therefore approx. 30 ms may pass from when an input value changes to when
the data read-out values change.
16-11 Power [HP]
Range:
Function:
0 HP
*
[0 to 1000 HP]
View the motor power in HP. The value shown is calculated on the basis of the actual motor voltage and motor
current. The value is filtered, and therefore approximately 30 ms may pass from when an input value changes
to when the data read-out values change.
16-12 Motor Voltage
Range:
Function:
0.0V
*
[0.0 - 6000.0 V]
View the motor voltage, a calculated value used for controlling the motor.
16-13 Motor Frequency
Range:
Function:
0.0Hz
*
[0.0 - 6500.0 Hz]
View the motor frequency, without resonance dampening.
16-14 Motor Current
Range:
Function:
0 A
*
[0 to 1856 A]
View the motor current measured as a mean value, IRMS. The value is filtered, and thus approximately 30 ms
may pass from when an input value changes to when the data read-out values change.
16-15 Frequency [%]
Range:
Function:
0.00%
*
[0.00 - 0.00 %]
View a two-byte word reporting the actual motor frequency (without resonance dampening) as a percentage
(scale 0000-4000 Hex) of par. 4-19
Max. Output Frequency
. Set par. 9-16 index 1 to send it with the Status Word
instead of the MAV.
16-16 Torque
Range:
Function:
0.0Nm
*
[-3000.0 - 3000.0 Nm]
View the torque value with sign, applied to the motor shaft. Linearity is not exact between 160% motor current
and torque in relation to the rated torque. Some motors supply more than 160% torque. Consequently, the min.
value and the max. value will depend on the max. motor current as well as the motor used. The value is filtered,
and thus approx. 30 ms may pass from when an input changes value to when the data read-out values change.
16-17 Speed [RPM]
Range:
Function:
0 RPM
*
[0 - 0 RPM]
View the actual motor RPM. In open loop or closed loop process control the motor RPM is estimated. In speed
closed loop modes the motor RPM is measured.
16-18 Motor Thermal
Range:
Function:
0 %
*
[0 - 100 %]
View the calculated thermal load on the motor. The cut-out limit is 100%. The basis for calculation is the ETR
function selected in par.1-90.
16-19 KTY Sensor Temperature
Range:
Function:
0°C
*
[0 - xxx °C]
Returning the actual temperature on KTY sensor buil into the motor.
See par. 1-9*.
2. How to Programme
FC 300 Programming Guide
158
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark
2