NB!
The options depend on installed option.
10-01 Baud Rate Select
Option:
Function:
[16]
10 Kbps
[17]
20 Kbps
[18]
[19]
50 Kbps
100 Kbps
[20]
*
125 Kbps
[21]
250 Kbps
[22]
500 Kbps
Select the fieldbus transmission speed. The selection must correspond to the transmission speed of the master
and the other fieldbus nodes.
10-02 MAC ID
Range:
Function:
63
*
[0 - 127]
Selection of station address. Every station connected to the same network must have an unambiguous address.
10-05 Readout Transmit Error Counter
Range:
Function:
0
*
[0 - 255]
View the number of CAN control transmission errors since the last power-up.
10-06 Readout Receive Error Counter
Option:
Function:
[0]
0 - 255
View the number of CAN control receipt errors since the last power-up.
10-07 Readout Bus Off Counter
Range:
Function:
0
*
[0 - 255]
View the number of Bus Off events since the last power-up.
2.13.3. 10-1* DeviceNet
Parameters specific to the DeviceNet fieldbus.
10-10 Process Data Type Selection
Option:
Function:
Select the Instance (telegram) for data transmission. The Instances available are dependent upon the setting
of par. 8-10
Control Word Profile
.
When par. 8-10 is set to [0]
FC profile
, par. 10-10 options [0] and [1] are available.
When par. 8-10 is set to [5]
ODVA
, par. 10-10 options [2] and [3] are available.
Instances 100/150 and 101/151 are Danfoss-specific. Instances 20/70 and 21/71 are ODVA-specific AC Drive
profiles.
For guidelines in telegram selection, please refer to the DeviceNet Operating Instructions.
Note that a change to this parameter will be executed immediately.
[0]
Instance 100/150
[1]
Instance 101/151
[2]
Instance 20/70
[3]
Instance 21/71
2. How to Programme
FC 300 Programming Guide
120
MG.33.M3.02 - VLT
®
is a registered Danfoss trademark
2