SiUS30-604
Field Setting
Test Operation
131
Procedures for charging additional refrigerant.
Additional refrigerant charge procedure (2)-by Additional refrigerant charge operation
To learn the system settings for additional refrigerant charging, refer to the [Service Precaution]
label attached on the back of the electric box lid in the outside unit.
1. Fully open all stop valves (valve A and valve B must be left fully closed).
2. After ten minutes, fully close liquid line stop valve and then, open the valve by turning 180°.
Start the additional refrigerant charge operation.
See [Service precautions] Label for detail.
If it is difficult to charge the refrigerant additionally, decrease the water temperature or warm the
refrigerant tank.
(Warm the refrigerant tank with a stupe or a warm hot water of 104 °F or less.)
3. After the system is charged with a specified amount of refrigerant, press the RETURN button
(BS3) on the PC board (A1P) in the outside unit to stop the additional refrigerant charge
operation.
4. Immediately open both liquid-side and gas-side stop valve.
(If do not open the stop valve immediately, liquid seal may cause the pipe to burst.)
Note
If the refrigerant cylinder is siphonal, set it upright while charging additional refrigerant.
Stop valve operation procedure
Caution
Do not open the shutoff valve until “Checking of device and installation conditions” are completed. If
the stop valve is left open without turning on power, it may cause refrigerant to buildup in the
compressor, leading to insulation degradation.
Opening stop valve
1. Remove the cap and turn the valve counterclockwise with the hexagon wrench (JISB4648).
2. Turn it until the shaft stops.
Do not apply excessive force to the stop valve. Doing so may break the valve body, as the valve
is not a backseat type. Always use the special tool.
3. Make sure to tighten the cap securely.
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...