Troubleshooting (OP: Unified ON/OFF Controller)
SiUS30-604
246
Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2842)
Is the
reset switch
of all optional controllers
for centralized
control set to
“normal”?
Is
transmission wiring
disconnected or wired
incorrectly?
Correct the setting of the
unified ON / OFF controller’s
switch for setting each
address and reset the power
supply of the unified ON /
OFF controller.
Refer to failure diagnosis for
central remote controller or
schedule timer.
NO
YES
YES
NO
NO
Fix the wiring correctly.
Set reset switch to
“normal”.
NO
NO
YES
YES
YES
Is the
power supply
turned on for all
optional controllers for
centralized
control?
Reset power supply
simultaneously for all optional
controllers for centralized
control.
NO
YES
Has a once
connected optional
controller for centralized
control been disconnected
or its address
changed?
Is the
central remote
controller or schedule
timer displaying a
malfunction?
Is
a central remote
controller or schedule timer
connected?
Turn on power supply for
all optional controllers for
centralized control.
NO
YES
NO
Is the setting
of the unified
ON / OFF controller’s
switch for setting
each address
duplicated?
Are
two or more unified
ON / OFF controllers
connected?
YES
2A
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...