Normal Control
SiUS30-604
68
Function
5.3
Heat Exchange Mode in Heating Operation or
Simultaneous Cooling / Heating Operation
In heating or simultaneous cooling / heating operation, a target condensing and evaporating
temperature can be secured by switching the water heat exchanger of the outside unit into
evaporator or condenser with load.
One outside unit installation
Two outside units installation
∆
GR>0
∆
GR
<0
∆
GR<0
∆
GR>0
Master unit
ON
(Evaporator)
Four-way changeover valve for
heat exchanger [Y7S] (For the
application of heat exchanger)
Content of the control of
electronic expansion valve [Y1E]
Control of heat exchange
capacity balance
Master unit
OFF
(Condenser)
Four-way changeover valve for
heat exchanger [Y7S] (For the
application of heat exchanger)
Content of the control of
electronic expansion valve [Y1E]
Control of heat exchange
capacity balance
Note 1:
∆
GR=Target of heat exchange capacity balance
– Actual measurement of heat balance
∆
GR>0: Insufficient evaporation
(Excessive condensation)
∆
GR<0: Insufficient condensation
(Excessive evaporation)
2: Control of heat exchange capacity balance
Control the electronic expansion valve so that Te or Tc
will obtain the target value.
Master unit
OFF
(Condenser)
Slave unit 1
OFF
(Condenser)
Four-way changeover valve for
heat exchanger [Y7S] (For the
application of heat exchanger)
Content of the control of
electronic expansion valve [Y1E]
Control of heat exchange
capacity balance
Control of heat exchange
capacity balance
Master unit
OFF
(Condenser)
Slave unit 1
ON
(Evaporator)
Four-way changeover valve for
heat exchanger [Y7S] (For the
application of heat exchanger)
Content of the control of
electronic expansion valve [Y1E]
Control of heat exchange
capacity balance
0 pulse
Master unit
OFF
(Condenser)
Slave unit 1
ON
(Evaporator)
Four-way changeover valve for
heat exchanger [Y7S] (For the
application of heat exchanger)
Content of the control of
electronic expansion valve [Y1E]
Control of heat exchange
capacity balance
Control of heat exchange
capacity balance
Master unit
ON
(Evaporator)
Slave unit 1
ON
(Evaporator)
Four-way changeover valve for
heat exchanger [Y7S] (For the
application of heat exchanger)
Content of the control of
electronic expansion valve [Y1E]
Control of heat exchange
capacity balance
0 pulse
Master unit
ON
(Evaporator)
Slave unit 1
ON
(Evaporator)
Four-way changeover valve for
heat exchanger [Y7S] (For the
application of heat exchanger)
Content of the control of
electronic expansion valve [Y1E]
Control of heat exchange
capacity balance
Control of heat exchange
capacity balance
∆
GR>0
∆
GR
<0
∆
GR>0
∆
GR
<0
∆
GR>0
∆
GR
<0
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...