Stop
SiUS30-604
60
Function
In heating operation or simultaneously in cooling / heating operation :
The system operates in mode A or mode B listed in the table below.
The changeover operation for mode A and B is performed for the reason that the required refrigerant amount varies
depending on the indoor unit operation capacity.
2.1.3 Abnormal Stop
In order to protect compressors, if any of the following items has an abnormal value, the system will
make “stop with thermostat OFF” and the malfunction will be determined according to the number
of retry times.
Parts name
Symbol
Electrical
symbol
Mode A operation
Mode B operation
Compressor
—
(M1C)
OFF
OFF
Inverter cooling fan
—
(M1, 2F)
OFF
OFF
4 way valve (Main)
20S1
(Y5S)
Holding
Holding
4 way valve (for heat exchanger)
20S2
(Y7S)
Holding
Holding
Main heat exchanger electronic exp.
valve
EV1
(Y1E)
0 pulse
0 pulse
Sub-cooling electronic exp. valve
EV3
(Y3E)
0 pulse
0 pulse
Hot gas bypass solenoid valve
SVP
(Y1S)
OFF
OFF
Water heat exch. oil return solenoid valve
SVE
(Y2S)
OFF
OFF
Receiver gas charging solenoid valve
SVL
(Y3S)
ON
OFF
Receiver gas discharge solenoid valve
SVG
(Y4S)
OFF
OFF
Non-operation unit liquid pipe stop
solenoid valve
SVSL
(Y6S)
OFF
ON
Mode transition conditions
To Mode B when No gas
shortage signal is sent
from indoor unit
To Mode A when gas
shortage signal is sent
from indoor unit
Ending conditions
Slave units are required to operate.
Mode A : Master unit collects refrigerant.
Mode B : Slave unit storage refrigerant.
Master
unit
Slave
unit
∗
Mode A or B operation
Item
Judgement value
Retry number
Malfunction code
1. Low pressure abnormal
10.1psi
3 times in 60 minutes
E4
2. High pressure abnormal
537psi
2 times in 30 minutes
E3
3. Discharge temperature
abnormal
275°F
2 times in 100 minutes
F3
4. Power supply abnormal
Reverse phase
No retry
U1
5. Inverter current abnormal
17A for 5 sec. (380V power supply)
25.1A for 260 sec. (220V power supply)
3 times in 60 minutes
L8
6. Radiation fin temperature
abnormal
192.2°F
3 times in 60 minutes
L4
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...