Precautions for New Refrigerant (R-410A)
SiUS30-604
288
Precautions for New Refrigerant (R-410A)
2. Torque wrench
Specifications
2
Dimension B
Unit:mm
No change in tightening torque
No change in pipes of other sizes
Differences
2
Change of dimension B
Only 1/2", 5/8" are extended
3. Vacuum pump with check valve
Specifications
2
Discharge speed
z
Maximum degree of vacuum
50 l/min (50Hz)
Select a vacuum pump which is able to keep
60 l/min (60Hz)
the vacuum degree of the system in excess of
2
Suction port UNF7/16-20 (1/4 Flare)
–14.6 psi (5 torr or 5000 micron or – 755 mmHg).
UNF1/2-20 (5/16 Flare) with adapter
Differences
2
Equipped with function to prevent reverse oil flow
2
Previous vacuum pump can be used by installing adapter.
Nominal size
Class-1
Class-2
Previous
1/2
24
26
24
5/8
27
29
27
Dimension B
For class-1: R-407C
For class-2: R-410A
Vacuum pump adapter
Reverse flow preventive
vacuum adapter
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...