Troubleshooting by Indication on the Remote Controller
SiUS30-604
180
Troubleshooting
∗
1: Coil check method for the moving part of the electronic expansion valve
Discount the electronic expansion valve from the PC board and check the continuity between the
connector pins.
(Normal)
{
: Continuity
× : No continuity
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
1. White
×
{
Approx.
300
Ω
×
{
Approx.
150
Ω
×
2. Yellow
×
{
Approx.
300
Ω
×
{
Approx.
150
Ω
3. Orange
×
{
Approx.
150
Ω
×
4. Blue
×
{
Approx.
150
Ω
5. Red
×
6. Brown
M
White (1)
Yellow
(2)
Blue
(4)
Brown
(6)
Red (5)
Orange (3)
φ
1
φ
2
φ
4
φ
3
(1) White
(2) Yellow
(3) Orange
(4) Blue
(5) Red
(6) Brown
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...