SiUS30-604
Field Setting
Test Operation
109
Selection of
Control Mode
No.
Select whether to accept or to reject the operation from the remote controller regarding the operation,
stop, temperature setting and operation mode setting, respectively, and determine the particular control
mode from the rightmost column of the table below.
(Example)
C : 3P171361-1
Operation by remote
controller (at time of
unified operation by
centralized control)
Operation by remote
controller (at time of
unified operation by
centralized control)
Operation
mode setting
by remote
controller
Temperature
control by
remote
controller
Stop by
remote
controller
[Rejection]
[Rejection]
[Rejection]
[Acceptance]
[Acceptance]
The control
mode is “ 1 ”.
Operation
mode
Control by remote controller
Control
mode
Operation
Stop
Temperature
control
Operation
mode setting
Unified operation,
individual operation by
central remote
controller, or operation
controlled by timer
Unified stop, individual
stop by central remote
controller, or timer stop
ON/OFF control
impossible by
remote controller
Rejection
(Example)
Rejection
(Example)
Rejection
(Example)
Rejection
Acceptance
0
Rejection
10
Acceptance
(Example)
Acceptance
(Example)
1 (Example)
Rejection
11
Only OFF control
possible by remote
controller
Acceptance
Rejection
Acceptance
2
Rejection
12
Acceptance
Acceptance
3
Rejection
13
Centralized
Acceptance
Rejection
Acceptance
4
Rejection
14
Acceptance
Acceptance
5
Rejection
15
Individual
Acceptance
Rejection
Acceptance
6
Rejection
16
Acceptance
Acceptance
7
Rejection
17
Timer operation
possible by remote
controller
Acceptance
(During timer at
ON position only)
Rejection
(During timer at OFF
position)
Rejection
Acceptance
8
Rejection
18
Acceptance
Acceptance
9
Rejection
19
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...