Troubleshooting (OP: Schedule Timer)
Troubleshooting
241
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Disconnect the schedule
timer's individual / combined
connector and reset the
power supply for all optional
controllers for centralized
control simultaneously.
Arrange so that the connector
for setting master controller is
connected to one controller
for centralized control and
reset the power supply for all
optional controllers for
centralized control
simultaneously.
Disconnect the connector for
setting master controller from
the master controller, connect
to another optional controller
for centralized control and
simultaneously reset all
optional controllers for
centralized control again. The
controller connected by the
connector for setting master
controller when the malfunction
is cleared is defective and
must be replaced.
Reset the power supply
for all optional controllers
for centralized control
simultaneously.
YES
YES
NO
Is the schedule
timer connected?
Are
there two or
more optional
controllers
for centralized control
connected with the
connector for setting
master
controller?
YES
Is the schedule
timer’s individual/combined
connector connected?
NO
NO
Cannot be used in
combination with a wiring
adaptor for electrical
appendices. Remove the
wiring adaptor for electrical
appendices and reset the
power supply for all optional
controllers for centralized
control simultaneously.
YES
Is the wiring
adaptor for electrical
appendices
connected?
NO
Schedule timer and parallel
interface cannot be used in
combination. Disconnect
either the schedule timer or
parallel interface and reset
the power supply for
simultaneously centralized
control.
YES
Is a parallel interface
connected?
NO
If the malfunction is still not cleared:
(V2839)
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...