Specifications
SiUS30-604
22
Specifications
Notes:
1.
★
1 Indoor temp. : 80°FDB, 67°FWB / inlet water temp. : 85°F / outlet water temp. : 95°F
Equivalent piping length : 25ft, level difference : 0ft.
★
2 Indoor temp. : 70°FDB, 60°FWB / inlet water temp. : 70°F / Equivalent piping length : 25ft, level difference : 0ft.
★
3 In the case of heat pump system, suction gas pipe is not used.
★
4 In the case of heat recovery system.
★
5 In the case of heat pump system.
2. This unit cannot be installed outdoors.
Install indoors (Machine room etc.).
3. Hold ambient condition at 35~95°F, ~80%RH
Heat rejection from the casing : 0.71kW×3
4. There are some cases where capacity decreases depending on operating states.
Model Name (Combination Unit)
RWEYQ252MTJU
Model Name (Combination Unit)
RWEYRWEYRWEYQ84MTJU
★
1 Cooling Capacity
Btu / h
252,000
★
2 Heating Capacity
Btu / h
283,500
Casing Color
Ivory White (5Y7.5/1)
Dimensions: (H×W×D)
in
(39-3/8×30-3/4×21-11/16)×3
Heat Exchanger
Stainless Steel Plate Type
Comp.
Type
Hermetically Sealed Scroll Type
Piston Displacement
m³/h
13.66×3
Number of Revolutions
r.p.m
6,450×3
Motor Output×Number
of Units
kW
4.0×3
Starting Method
Soft Start
Connecting
Pipes
Liquid Pipe
in
3/4 in C1220T (Flare Connection) -Main Line-
Suction Gas Pipe
in
1-3/4 in C1220T (Brazing Connection)
★
3 -Main Line-
Discharge Gas Pipe
in
★
4 1-1/8 in C1220T,
★
5 1-3/8 in C1220T (Brazing Connection) -Main Line-
Water inlet
1 1/4 FPT Female Thread
Water outlet
1 1/4 FPT Female Thread
Drain outlet
1/2 FPS Female Thread
Machine Weight (Mass)
Lbs
330+330+330
Safety Devices
High Pressure Switch, Inverter Overload Protector, Fusible Plugs
Capacity Control
%
8~100
Refrigerant
Refrigerant Name
R-410A
Charge
Lbs
11.5+11.5+11.5
Control
Electronic Expansion Valve
Refrigerator Oil
Synthetic (Ether) Oil
Standard Accessories
Installation Manual, Operation Manual, Connection Pipes, Clamps, Strainer, Conduit Mounting Plate
Drawing No.
4D054576C
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...