SiUS30-604
Troubleshooting by Remote Controller
Troubleshooting
149
System
U0
8
7
9
Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
207
U1
9
9
9
Reverse phase / open phase
209
U2
9
9
9
Power supply insufficient or instantaneous failure
210
U3
9
9
9
Check operation is not conducted.
212
U4
9
9
9
Malfunction of transmission between indoor and outside
units
213
U5
9
9
9
Malfunction of transmission between remote controller
and indoor unit
215
U5
7
8
7
Failure of remote controller PC board or setting during
control by remote controller
215
U7
9
9
9
Malfunction of transmission between outside units
216
U8
9
9
7
Malfunction of transmission between master and slave
remote controllers (malfunction of slave remote
controller)
218
U9
9
9
9
Malfunction of transmission between indoor unit and
outside unit in the same system
219
UA
9
9
9
Excessive number of indoor units etc.
221
UC
8
8
8
Address duplication of central remote controller
223
UE
9
9
9
Malfunction of transmission between central remote
controller and indoor unit
224
235
UF
9
9
9
Refrigerant system not set, incompatible wiring / piping
226
UH
9
9
9
Malfunction of system, refrigerant system address
undefined
227
Centralized
Control
and
Schedule
Timer
M1
8
or
7
9
9
PC board defect
229
237
M8
8
or
7
9
9
Malfunction of transmission between optional controllers
for centralized control
230
238
MA
8
or
7
9
9
Improper combination of optional controllers for
centralized control
232
240
MC
8
or
7
9
9
Address duplication, improper setting
234
242
Heat
Reclaim
Ventilation
64
8
7
9
Indoor unit’s air thermistor error
—
65
8
7
9
Outside air thermistor error
—
6A
8
7
9
Damper system alarm
—
6A
9
9
9
Damper thermistor error
—
6F
8
7
9
Malfunction of simple remote controller
—
6H
8
7
9
Malfunction of door switch or connector
—
94
9
9
9
Internal transmission error
—
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...