SiUS30-604
Field Setting
Test Operation
129
3.2.5 Setting of Refrigerant Additional Charging Operation
When additional refrigerant is not charged all with outside unit in stop mode, operate the outside
unit and charge the liquid refrigerant from the service port of liquid stop value. The additional
charging operation is activated by pushbutton switch on the outside unit PC board.
[Additional refrigerant charge total flow]
Confirm DISCHARGE,
SUCTION and LIQUID Stop
valves closed.
Is all refrigerant charged?
Is all refrigerant charged?
YES
YES
NO
Turn off the power.
Charge through Service port of
LIQ. Stop valve.
Open DISCHARGE GAS,
LIQUID, SUCTION GAS
Stop
valve.
Open LIQUID Stop valve.
Disconnect charge hose.
END of charge method.
STOP refrigerant charge model
STEP 1
Additional
charge
without
Compressor
operation
Start additional refrigerant charge mode.
(Setting Mode 2 : Refer operation procedure
detail on next page.)
Open DISCHARGE & SUCTION
GAS
Stop valve.
LIQUID side stop valve:
1. Fully open the liquid side stop valve.
2. After ten minutes, fully close liquid line stop
valve and then, open the valve by turning
180º.
Note: The stop valve operations are different
from heat pump and heat recovery
connection, refer following page for
detail.
STEP 2
Additional
charge
with
Compressor
operation
(V2892)
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...