Troubleshooting (OP: Unified ON/OFF Controller)
SiUS30-604
248
Troubleshooting
5.3
Display “Under Host Computer Integrate Control” Blinks
(Repeats Double Blink)
Remote
Controller
Display
“under host computer integrated control” (Repeats double blink)
Applicable
Models
Unified ON/OFF controller
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Decision
Conditions
When no central control addresses are set to indoor units.
When no indoor units are connected within the control range.
Supposed
Causes
Central control address (group No.) is not set for indoor unit.
Improper address setting
Improper wiring of transmission wiring
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2844)
Is the switch
for setting each address
set correctly?
Is
the transmission
wiring disconnected or
wired incorrectly?
Replace the PC board of the
unified ON/OFF controller.
Fix the wiring correctly.
Set by remote controller the
central control address for all
indoor units connected to the
central control line.
YES
YES
Set the switch for setting each
address correctly and
simultaneously reset the power
supply for all optional controllers
NO
NO
NO
YES
Is the central
control address (group No.)
set for the
indoor unit?
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...