Troubleshooting by Indication on the Remote Controller
SiUS30-604
184
Troubleshooting
2.20
“
HJ
”
Malfunction of Water system
Remote
Controller
Display
HJ
Applicable
Models
RWEYQ60, 72, 84MTJU
Method of
Malfunction
Detection
Detect abnormalities using the thermistor on the side of the heat exchanger gas.
Detect turned off interlock circuit.
(When interlock setting is provided.)
Malfunction
Decision
Conditions
When temperature on the heat exchanger gas side (R4T) drops remarkably with the smallest
operation step (52 Hz) of the compressor
With interlock setting provided, when interlock circuit is turned off.
Supposed
Causes
Clogged water piping system
Insufficient heat exchanger water
Dirty heat exchanger
Disconnected connector
Faulty thermistor on the heat exchanger gas side
Faulty low pressure sensor
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...