Troubleshooting by Indication on the Remote Controller
SiUS30-604
178
Troubleshooting
Troubleshooting
YES
NO
NO
YES
YES
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
UVWN wire connection
proper?
Is it a
high differential
pressure at the time of
start-up (72.5psi or
more)?
(
∗
1)
Restart operation after
resetting operation.
Disconnect the connection between
the compressor and the inverter
and turn on power transistor check
mode setting using “Setting Mode
2” on the outside unit PCB.
Measure inverter output voltage.
Note: Take measurements
while frequency is stable.
Eliminate the causes.
The hot gas bypass valve
may not be opened.
Check it.
NO
YES
The inverter
compressor operates
normally.
Replace the compressor.
NO
Replace the inverter PCB.
YES
Replace the inverter compressor.
Open the stop valve.
∗
1 : Difference in pressure between high and low pressures before start-up
∗
2 : The quality of the power transistor diode module can be assessed also by means of
measurement of resistance between terminals (page 281, 282).
Is the stop
valve opened?
Connect properly.
Inverter
output voltage
among 3 phases is
within ±5V of power
supply.
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...