Field Setting
SiUS30-604
134
Test Operation
3.2.8 Check Operation
To prevent any trouble in the period of installation at site, the system is provided with a test
operation mode enabling check for incorrect wiring, stop valve left in closed, coming out (or
misplacing with suction pipe thermistor) of discharge pipe thermistor and judgment of piping length,
refrigerant overcharging, and learning for the minimum opening degree of motorized valve.
Unit stopping
Press the TEST button for 5 seconds.
10 sec to 10 minutes
LED display (H1P~H7P) (
8
:
ON
9
:
BLINKING
3
:
OFF)
3383333
3933338
Pressure equalizing
Step 1
3~5 minutes
10 minutes
3 minutes
10 sec. ~ 5 minutes
3933383
Cooling start control
Step 2
3933388
3938333
3938338
3383333
3883333
Stability waiting operation
Step 3
Pump down residual operation
Step 7
5 minutes
Standby for restarting
Completion
Step 8
•
Stop valve close check
•
Wrong wiring check
•
Refrigerant over change check
•
Piping length check
3933833
3933838
3933883
3933888
Judgment function
Step4~6
CHECK OPERATION FUNCTION
: Normal completion
: Abnormal completion
Summary of Contents for VRV - WII
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Page 13: ...Introduction SiUS30 604 xii...
Page 27: ...Capacity Range SiUS30 604 14 General Information...
Page 49: ...Specifications SiUS30 604 36 Specifications...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Page 309: ...SiUS39 601 iv Index...