Troubleshooting by Indication on the Remote Controller
Troubleshooting
173
2.14
“
E3
”
Outside Unit:
Actuation of High Pressure Switch
Remote
Controller
Display
E3
Applicable
Models
RWEYQ60, 72, 84MTJU
Method of
Malfunction
Detection
Detect conductive property of the high pressure switch with the protector circuit.
Malfunction
Decision
Conditions
When the protector circuit is partially opened
(For reference) Working pressure for the high pressure switch
Working pressure: 580psi
Return pressure: 413psi
Supposed
Causes
High pressure switch operation
Faulty high pressure switch
Faulty main PCB
Temporal power failure
Faulty high pressure sensor
Insufficient heat source water
Dirty water heat exchanger